SINGLE-PHASE STATIC METER 

DOMOTAX TeLeGeST PRIME

 

 
INSTRUCTIONS ON USE 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
DESCRIPTION: 

The DOMOTAX TeLeGeST PRIME is a single-phase static meter for 
measuring both active and reactive energy. It is directly connected to the 
interior installation, with communications capabilities and functions that 
allow telemanagement. 

It complies with the requirements of Directive 2014/32/UE, RD 244/2016 
and ORDEN ITC/3022/2007. 

 
 
 
 
 
 
 
 
 
 
 
Main characteristics: 

1. 

Register for measuring both active and reactive energy 
consumption, in import and export. 

2. 

Register for measuring both inductive and capacitive reactive 
energy consumption. 

3. 

Six tariff periods, each with its maximum power register. 

4. 

A single pulsed LED configured for active or reactive energy. 

5. 

The equipment measures the following electrical magnitudes in any 
quadrant: 

- Active power 
- Reactive power 
- rms voltage 
- rms current 
-  Phi, cos phi 

6. 

It is fitted with an omnipolar circuit breaker. 

7. 

Communications may be remote (via a PLC) or local (via an optical 
interface). 

8. 

Detects and registers the opening of terminal covers. 

9. 

Detects and registers power supply circuit breaker operations and 
resets. 

 

INSTALLATION  

The seals may only be removed by authorised personnel. 
MOUNTING: The equipment is secured by means of the three holes that 
form the securing triangle according to DIN 43 857, using the following 
mounting dimensions: 

 
 
 
 
 
 
 

 
 
 
 
 
 

CONNECTION

 

Connect according to the wiring diagram, depending on model 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
During wiring, it is essential to secure the wire in place using both 
screws. 
 
 
 
 
 
 
The power terminals accept wires up to 7.5 mm in diameter (from 6 to 25 
mm

wire section) using two M6 screws. 

Auxiliary terminal block accepts wires up to 2.5 mm diameter. 
 

DATA DISPLAY 

Data is automatically shown on the screen. Another way to display data 
is to repeatedly press the Info button. 
 

CHANGING SUMMER-WINTER TIME 

Summer-winter time changeover is automatically performed on the 
official dates. 
 

CLOSING 

A time period can be closed in three different ways: 

-

  Manually, by pressing the Close key 

-

  By means of remote optical communications 

-

  Automatically at the programmed time, on the programmed date of 

each month. 

 

TECHNICAL SPECIFICATIONS 

Reference voltage and frequency: 

230 Vac     50 Hz. 

Protection class: 

Class II 

Own consumption in voltage circuit: 

 10 VA; 

  2 W, in normal 

operating regime, without PLC 
transmission or special function 
operations 

Active precision class: 

Class B according to EN 50470-3 

Reactive precision class: 

Class 2 according to EN 62053-23  

Active current values 

-

  Start-up current: 

20 mA for cos 

φ

 

=1 

-

  Minimum current: 

0.1 A 

-

  Transition current: 

1 A 

-

  Reference current: 

10 A 

-

  Maximum current: 

60 A 

Reactive start-up current: 

50 mA for sin 

φ

 

=1 

LED constant:  

4,000 imp / kWh / kVArh  

Operating precision 

± 0.5 s/24h at 23 ºC using quartz 

Operating backup 

3 years for the lithium battery  

Operating temperature: 

-25 ºC to +70 ºC 

 
OTHER TECHNICAL SPECIFICATIONS 

Protection type 

IP 51 according to EN 60529 

Optical communications 

According to EN 62056-21 

PLC communications: 

 

     CENELEC band:   

According to EN 50065-1 

     Modulation type 

OFDM according to PRIME 

     Application level 

DLMS 

Auxiliary contact breaking power 
According to model 

0.5 A / 250 Vac 

 
 
 
 
 
 
 

COVER

ACTIVE AND REACTIVE

PULSE LED

OPTICAL

INTERFACE

PLC CONNECTION

STATUS INDICATOR

TERMINAL COVER

SEALABLE
SCREWS

SEALABLE

SCREWS

SEALABLE SCREWS

SEALABLE BUTTON
FOR MANUALLY RESETTING
THE MAXIMETER

ACCESSIBLE BUTTON

FOR OBTAINING ON-SCREEN
INFORMATION

DISPLAY SCREEN

108

142

"OBIS"

 CODE

ENERGY SENSE

DATA DIGITS

ACTIVE

REACTIVE

OPEN STATUS OF
BREAKER ELEMENTS

REACTIVE VERIFICATION

COMMUNICATIONS STATUS

ALARM

PHASE PRESENCE AND

CURRENT SENSE

ACTIVE

PERIOD

N

L

6

4

3

1

23 24

N

L

6

4

3

1