After-flow Time (factory-set to 1 second)
– After-flow time can be adjusted using the Oras Data Terminal (v. 2.4 or later).
Cleaning the Filter (see Figure 2)
If the water flow has decreased, this may be because the filter is clogged. Clean the filter as follows:
– Shut off the water supply to the faucet.
– Unscrew the strainer (18) from the valve housing.
– Clean the strainer under running water.
– Screw the strainer back.
Changing the temperature regulator (see Figure 5)
Troubleshooting
Symptom
Cause / Solution
Water flow from the outlet does
– The sensing range is too low
not stop, or stops after 2 minutes
– Check that the photocell is clean
– The solenoid valve is damaged
Water flow is low and weak
– Filter is clogged
No water comes out of the faucet
– Check the water supply to the control box
– The solenoid valve is damaged
– Power failure
– The photocell is covered or damaged
– 6105 and 6135: the showerhead is not placed
properly in its wall bracket
– Check the fuse (17) inside the control box:
6104 and 6105: 0.1 A
6134 and 6135: 1 A
15 (52)