1. A second 3U PDP and the respective cable kit is required:
a. for a raised floor.
b. any time 9 or more T1200 pieces are added to a T1200 cabinet co-mingled with an ATCA shelf.
c. anytime 14 or more T1200 pieces are specified or zone 2 is populated with servers in a T1200
cabinet.
2. A 3U PDP is populated with breakers based on the strategy defined in the 3U PDP worksheet.
3. A 1U Filler panel is required above the second 3U PDP for thermal management.
4. All equipment in the network zone and application zones 1 - 3 are loaded and numbered from top
to bottom. Storage arrays are loaded starting at U34 for weight distribution purposes.
5. The first T5100 shelf is always loaded in zone 3 at bottom of cabinet, a second T5100 shelf is loaded
above the first shelf.
6. A 2U space is reserved at bottom of cabinet to accommodate raised floor power cable entry.
Tekelec 1200 Platform Components
The cabinet for the Tekelec 1200 (T1200) platform contains these components:
•
Power Distribution Panel (PDP)
•
•
•
•
•
Figure 4: Example of T1200 Application Cabinet Configuration
shows a T1200 application cabinet with 2
PDPs, 6 Ethernet switches, and 9 T1200 application servers installed.