Preparing for Installation
System Power Consumption
TABLE 59
Oracle Exadata Storage Expansion Rack Power Consumption
Comments
Full Rack
Half Rack
Quarter Rack
Maximum
Typical
12.6 kW
12.9 kVA
8.8 kW
9.0 kVA
6.9 kW
7.1 kVA
4.8 kW
5.0 kVA
3.4 kW
3.5 kVA
2.4 kW
2.5kVA
Related Information
■
“PDU Power Requirements” on page 290
■
“Grounding Requirements” on page 100
■
“Facility Power Requirements” on page 100
PDU Power Requirements
When ordering the Oracle Exadata Storage Expansion Rack, you must provide two
specifications:
■
Low or high voltage
■
Single or three phase power
Refer to the following tables for Oracle marketing and manufacturing part numbers.
Note -
Each Oracle Exadata Storage Expansion Rack has two power distribution units (PDUs).
Both PDUs in a rack must be the same type.
TABLE 60
PDU Choices
Voltage
Phases
Reference
Low
1
Table 61, “Low Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
Low
3
Table 62, “Low Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
High
1
Table 63, “High Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
290
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...