Preparing for Installation
High Voltage
Three Phase
Comments
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
TABLE 63
High Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack
High Voltage
Single Phase
Comments
kVA Size
15 kVA
Marketing part number
N/A
Manufacturing part number
N/A
Phase
1 ph
Voltage
220 to 240 VAC
Amps per PDU
72 A (3 inputs x24 A)
Outlets
42 C13
6 C19
Number of inputs
6
Input current
25 A max. per input
Data center receptacle
IEC 60309 32A 3-pin 250VAC IP44
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
TABLE 64
High Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack
High Voltage
Single Phase
Comments
kVA size
14.4 kVA
Marketing part number
N/A
Manufacturing part number
N/A
Phase
3 ph
Voltage
220/380 to 240/415 VAC
Amps per PDU
62.7 A (3 inputs x 20.9. A)
Outlets
42 C13
6 C19
Number of inputs
2 inputs x 25 A
Input current
25 A max. per phase
Data center receptacle
IEC 60309 32A, 5-pin 230/400 VAC
Outlet groups per PDU
6
292
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...