![Oracle Sun Netra X4270 Service Manual Download Page 194](http://html1.mh-extra.com/html/oracle/sun-netra-x4270/sun-netra-x4270_service-manual_1646169194.webp)
Install Fan Tray 2
4.
Set fan tray 2 aside on an antistatic mat.
5.
Consider your next step:
■
If you removed the fan assembly as part of another procedure, return to that procedure.
■
Otherwise, continue to
“Install Fan Tray 2” on page 194
.
Related Information
■
“Replacing the Media Bay Assembly” on page 93
■
“Replacing Fan Tray 0” on page 189
■
“Install Fan Tray 2” on page 194
■
“Replacing the Power Distribution Board” on page 203
Install Fan Tray 2
1.
Remove the replacement fan tray 2 from its packaging and place it on an
antistatic mat.
2.
Insert the replacement fan tray 2 in the slot with the airflow direction arrow
facing the rear of server.
194
Sun Netra X4270 Server • September 2015
Summary of Contents for Sun Netra X4270
Page 1: ...Sun Netra X4270 Server Service Manual Part No E23171 03 September 2015 ...
Page 2: ......
Page 10: ...10 Sun Netra X4270 Server September 2015 ...
Page 12: ...12 Sun Netra X4270 Server September 2015 ...
Page 36: ...36 Sun Netra X4270 Server September 2015 ...
Page 72: ...72 Sun Netra X4270 Server September 2015 ...
Page 100: ...100 Sun Netra X4270 Server September 2015 ...
Page 224: ...224 Sun Netra X4270 Server September 2015 ...
Page 230: ...WDT W WDT watchdog timers 230 Sun Netra X4270 Server September 2015 ...