Servicing Power Supplies
The server contains four power supplies, which provide 2 + 2 power redundancy. If you need to
replace a power supply, you can do so while the server is operating.
Note -
To take full advantage of the server's power redundancy, plug the four power supplies
into at least two separate power sources.
Caution -
This procedure requires that you handle components that are sensitive to electrostatic
discharge. This discharge can cause failure of server components.
These topics describe service procedures for the power supplies in the server.
■
“Power Supply Configuration” on page 147
■
“Power Supply and AC Power Connector LEDs” on page 150
■
“Determine Which Power Supply Is Faulty” on page 151
■
“Remove a Power Supply” on page 151
■
“Install a Power Supply” on page 153
■
“Verify a Power Supply” on page 156
Power Supply Configuration
Power supply units are accessed from the front of the server.
Servicing Power Supplies
147
Summary of Contents for SPARC T7-4
Page 1: ...SPARC T7 4 Server Service Manual Part No E54994 07 May 2017 ...
Page 2: ......
Page 10: ...10 SPARC T7 4 Server Service Manual May 2017 ...
Page 12: ...12 SPARC T7 4 Server Service Manual May 2017 ...
Page 86: ...86 SPARC T7 4 Server Service Manual May 2017 ...
Page 98: ...98 SPARC T7 4 Server Service Manual May 2017 ...
Page 110: ...110 SPARC T7 4 Server Service Manual May 2017 ...
Page 124: ...124 SPARC T7 4 Server Service Manual May 2017 ...
Page 142: ...142 SPARC T7 4 Server Service Manual May 2017 ...
Page 164: ...164 SPARC T7 4 Server Service Manual May 2017 ...
Page 192: ...192 SPARC T7 4 Server Service Manual May 2017 ...
Page 200: ...200 SPARC T7 4 Server Service Manual May 2017 ...
Page 208: ...208 SPARC T7 4 Server Service Manual May 2017 ...