Chapter 4
Servicing and Replacing Components
4-3
4.2
Identifying Firmware Versions
It might be helpful to identify firmware versions in the External I/O Expansion Unit
when troubleshooting problems. Firmware is located on the motherboard and on
each link card.
To identify versions of firmware, use the
ioxadm -v list
command. In the output,
firmware versions are listed in the column marked “
FW Ver”
.
This example shows five instances of firmware in an External I/O Expansion Unit
that is configured with two I/O boats:
■
IOX
in the Type column identifies the chassis, where the fan controller firmware is
located.
■
OP
in the Type column identifies the link cards, where the bridge controller
firmware is located. A link consists of two link cards, and there are two links in
this example (one link for each I/O boat), for a total of four link cards:
■
LINK
in the Location column identifies a link card in an I/O boat.
■
IOU#
n
-PCI#
n
in the Location column identifies a link card in a server.
Refer to the
ioxadm
(8) man page for more information.
XSCF>
ioxadm -v list
Location Type FW Ver Serial Num Part Num State
IOX@X04E IOX 2.4 XCX04E 5016937-03 On
IOX@X04E/PS0 A195 - T01180 3001701-03 On
IOX@X04E/PS1 A195 - T01097 3001701-03 On
IOX@X04E/IOB0 PCIX - XX00EL CF005016938/5016938-05 On
IOX@X04E/IOB0/LINK OP 2.4 XF01D3 CF005017040/5017040-03 On
IOU#0-PCI#3 OP 2.4 XF014C 5017040-03 On
IOX@X04E/IOB1 PCIE - XE00C1 CF005016939/5016939-04 On
IOX@X04E/IOB1/LINK OP 2.4 XF00W2 5017040-03 On
IOU#0-PCI#1 OP 2.4 XF01AX CF005017040/5017040-03 On
XSCF>