background image

OPW 623V Pressure / Vacuum Vent 

 

Page 1 

OPW Installation and Maintenance Instructions

 

 

OPW 623V Pressure / Vacuum Vent Valve 

 

 

IMPORTANT: 

Please read

 

these

 

warnings and use 

the assembly instructions completely and carefully 
before starting. Failure to do so may cause product 
failure, or result in environmental contamination due 
to liquid leakage into the soil, creating hazardous 
spill conditions.  
 

IMPORTANT:

 The OPW 623V Pressure / Vacuum 

vent is pre-assembled for your convenience and 
ease of installation. Check to make sure the unit is 
intact and undamaged and all parts have been 
supplied. Never substitute parts for those supplied. 
Doing so may cause product failure. 
 

WARNING-DANGER:

 Using electrically operated 

equipment near gasoline or gasoline vapors may 
result in a fire or explosion, causing personal injury 
and property damage. Be sure that the working area 
is free from such hazards, and always use proper 
precautions.  
NOTE: At all times when product is in the storage 
tank keep the vent pipe capped, so the vapors 
cannot escape into the environment.  

 
Notice:

 OPW products must be used in compliance 

with applicable federal, state, and local laws and 
regulations.  Product selection should be based on 
physical specifications and limitations and 
compatibility with the environment and material to be 
handled.  All illustrations and specifications in this 
literature are based on the latest production 
information available at the time of publication.  
Prices, materials, and specification are subject to 
change at any time, and models may be 
discontinued at any time, in either case, without 
notice or obligation. 

 
Standard Product Warranty

 

OPW warrants that products sold by it are free from 
defects in materials and workmanship for a period of 
one year from the date of manufacture by OPW 
(ECO products two years from date of manufacture.) 
Proof of purchase may be required.  As the 
exclusive remedy under this limited warranty, OPW, 
will at its sole discretion, repair, replace, or issue 
credit for future orders for any product that may 
prove defective within the one year date of 
manufacture period (repairs, replacements, or 
credits may be subject to prorated warranty for 
remainder of the original warranty period, complete 
proper warranty claim documentation required.)  
This warranty shall not apply to any product that has 
been altered in any way, which has been repaired by 

any party other than a service representative 
authorized by OPW, or when failure is due to 
misuse, or improper installation or maintenance.  
OPW shall have no liability whatsoever for special, 
incidental or consequential damages to any party, 
and shall have no liability for the cost of labor, 
freight, excavation, clean up, downtime, removal, 
reinstallation, loss of profit, or any other cost or 
charges. 
 
For any product certified to California 2001 
standards, OPW warrants that product sold by it are 
free from defects in material and workmanship for a 
period of one year from date of manufacture or one 
year from date of registration of installation not to 
exceed 15 months from date of manufacture by 
OPW. 
 
THIS WARRANTY IS IN LIEU OF ALL OTHER 
WARRANTIES, EXPRESS OR IMPLIED, AND 
SPECIFICALLY THE WARRANTIES OF 
MERCHANTABILITY AND FITNESS FOR A 
PARTICULAR PURPOSE.  THERE ARE NO 
WARRANTIES, WHICH EXTEND BEYOND THE 
DESCRIPTION ON THE FACE HEREOF. 
 
 

623V Series Performance 
Specifications:

 

This Pressure / Vacuum vent has been 
manufactured and tested to the following 
specifications:  Pressure leak rate not to exceed 
0.05 CFH at 2” W.C.  Vacuum leak rate not to 
exceed 0.21 CFH at -4” W.C.  The cracking pressure 
to be 2.5” to 6” W.C. and cracking vacuum to be -6 
to -10” W.C.  Tested using CARB Test Procedure 
TP-201.1E or applicable Phase I Executive Order.   
 

Torque Specification:

 

Vent Assembly 2” NPT, 35 ft-lbs minimum to 55 ft-
lbs maximum. 
 
 
 
 
 
 
 
 
 
 