background image

The 61ƒSTOP-1000 is an overfill prevention valve for

use with an aboveground storage tank (AST) where prod-
uct is pumped from a transport vehicle into the AST.
The valve is designed to stop the flow of product when
the tank is filled to a pre-determined level.

WARNING: THE 61ƒSTOP IS DESIGNED FOR
TIGHT-FILL APPLICATIONS AND MUST ONLY
BE USED WITH APPROPRIATE CONNECTIONS.
FAILURE TO PROPERLY CONNECT THE 
DELIVERY HOSE OR DISCONNECTING A 
LIQUID-FILLED LINE WILL RESULT IN AN
EXTREMELY HAZARDOUS SPILL WHICH MAY
RESULT IN PERSONAL INJURY, PROPERTY
DAMAGE, FIRE, EXPLOSION OR WATER AND
SOIL CONTAMINATION.

INSTALLATION

The 61ƒSTOP-1000 is packaged with a 2" diameter, 

4" long pipe nipple that is loosely threaded in the inlet
of the valve. A collar for attaching the assembly to a 
4" riser is loosely assembled over the 4" long nipple. 
A special adapter with a crossbar is loosely threaded on
the inlet end of the nipple. This nipple may be used on
single wall tanks if dimension “B” (see illustration) is
between 3" and 6". If “B” dimension is 5"- 6", push 
nipple down until the adaptor meets the collar.
However, the ullage will be affected by the length 
of dimension “B”.

For “B” dimensions greater than 6", a different

2" diameter nipple length will need to be determined. 
See illustration for determining dimension “C”.

Instructions for installations where the 

4" long nipple is adequate, simply proceed 
with the following steps:

1. Remove the special adapter from the inlet 

of the nipple.

2. Remove the collar and nipple from the inlet 

of the valve.

CAUTION! 

CARE MUST BE TAKEN TO PREVENT 

DAMAGE TO THE FLOAT AND LINKAGE.

3. Apply a gasoline-resistant sealant to the outlet end

of the nipple and install it into the inlet of the valve.

4. Apply a gasoline-resistant sealant to the inlet end

of the nipple and thread the adapter in place.

5. Tighten the three (3) set screws in the collar.

6. Stand the valve upright, lift the float and release 

it to make sure it works freely.

OPW

®

H-12676-M

February, 2000

Installation
Instructions

OPW 61ƒSTOP-1000 & -100M “THE STOPPER”

7. Apply a gasoline-resistant sealant to the threads of

the 4" fitting in the top of the tank. Slide the valve
assembly through the fitting.

8. Thread the collar onto the fitting. The valve is now

ready for operation.

Instructions for installations where a longer, 2" 

diameter nipple (dimension “C”) must be used, i.e., a
nipple length greater than 4". See Illustration for 
determining length of nipple.

If dimension “B” is greater than 6", proceed

with the following steps:

1. Determine dimension “C” (length of 2" diameter

nipple) by adding dimension “A” and “B” and 
subtracting 8":  A+B - 8"= C. 

Note: “A” dimension

must be a minimum of 7".

2. Cut and thread the new nipple which corresponds

to dimension “C”.

3. Remove adapter from the inlet of the existing 

nipple and slide the collar off the nipple.

4. Remove the existing nipple from the valve.

5. Apply a gasoline-resistant sealant to one end of the

new nipple and thread it into the inlet of the valve.

6. Apply a liberal amount of grease to the o-ring in the

collar and slide the collar onto the nipple with the
4" threaded end toward the valve for a distance of
1

1

4

". Tighten the 3 set screws.

7. Apply a gasoline-resistant sealant to the inlet end of

the nipple and thread the adapter in place.

8. Stand the assembly upright, lift the float and

release it to make sure it works freely.

9. Apply a gasoline-resistant sealant to the threads of

the 4" fitting in the top of the tank and slide the
valve assembly through the fitting.

10. Thread the collar onto the fitting. The valve is

now ready for operation. 

Note: OPW recommends using a drop tube, such

as the OPW 61FT Series with all 61ƒSTOPs.

OPERATING PROCEDURES

CAUTION: READ THESE INSTRUCTIONS 

CAREFULLY AND COMPLETELY BEFORE 
OPERATING THIS DEVICE.

The 61ƒSTOP-1000 “The Stopper” is provided 

a special adaptor which requires the appropriate
attachment for connection to achieve a tight fit.

CAUTION! 

OPERATIONS PROCEDURES CONTINUED

ON NEXT PAGE.

Summary of Contents for 61fSTOP-1000

Page 1: ...e valve upright lift the float and release it to make sure it works freely OPW H 12676 M February 2000 Installation Instructions OPW 61ƒSTOP 1000 100M THE STOPPER 7 Apply a gasoline resistant sealant to the threads of the 4 fitting in the top of the tank Slide the valve assembly through the fitting 8 Thread the collar onto the fitting The valve is now ready for operation Instructions for installat...

Page 2: ...e se reduzca la presión en la manguera CUIDADO SI SE TRATA DE DESCONECTAR EL ACOPLADOR CUANDO HAY PRESION EN LA MANGUERA SE DERRAMARA PRODUCTO 4 Cierre la pistola y desacople la conexión despacio 5 Remueva la pistola cuidadosamente y reemplace la tapa OPW ofrece conector con bloqueo de leva en nuestra pistola manual estándar 190 para ser usada con The Stopper Esta nueva conexión con bloqueo de lev...

Page 3: ... the pressure in the hose to be reduced OPW offers a cam lock connector for our standard 190 manual nozzle for use with The Stopper This new cam lock connection provides for reliable high flow and mess free bulk fuel deliveries Additional nozzle features include Lightweight aluminum body dual poppets for easy opening against inlet pressure four position hold open latch and large lever area for max...

Page 4: ...resistente a la gasolina al extremo de salida del niple e instálelo en la entrada de la válvula 4 Aplique un sellador resistente a la gasolina al extremo de entrada del niple y enrosque el adaptador 5 Apriete los tres 3 tornillos en el collar 6 Posicione la válvula hacia arriba levante el flotador y déjelo ir para asegurarse que está trabajando correcta mente 7 Aplique un sellador resistente a la ...

Reviews: