background image

Be careful that flue pipe does not enter into the free section of the chimney.

Maintain the correct distances specified by building regulations between the flue pipe and 
combustible material.

This appliance must never be connected to a shared flue system.

If the chimney pressure is too low or too high this may cause problems with the working of 
the stove.

3.2. Safety rules

During the installation of the stove, all the building regulation and safety requirements 
must be complied with, with particular reference to the recommendations of Approved 
Document J.

The appliance must be installed on a floor with an adequate load-bearing capacity. If an 
existing construction doesn't meet these prerequisites then suitable measures (e.g. a load 
distribution plate) shall be taken to achieve it.

Pay attention to minimum distance required from combustible materials.

A wooden mantelpiece should not be used above an insert stove.

3.3 Minimum distances to combustibles

A

1600mm

In the area of thermal radiation

B1

200mm

Back space between the wall and stove

B2

500mm

Side space between combustible wall and stove

6

Summary of Contents for Tempo 100

Page 1: ...OPERATION AND INSTALLATION MANUAL OPUS TEMPO...

Page 2: ...FIRED BY DESIGN 1...

Page 3: ...eneral information about the working of the stove 8 5 1 Starting the stove 8 5 2 Layout and usage of air regulators 9 5 3 Suitable materials for lighting 9 5 4 Emptying the ashpan 10 5 5 Cleaning and...

Page 4: ...d 21 of the Clean Air Act 1993 by section 15 of the Deregulation Act 2015 Similarly in Scotland appliances are exempted by publication on a list by Scottish Ministers under section 50 of the Regulator...

Page 5: ...inner and outer walls of the stove This warm air is then spread by convection around the room 2 General National and European standards local construction regulations fire protection law and regulatio...

Page 6: ...e pipe connection The stove will not burn correctly and efficiently unless it is connected to a properly working chimney The chimney draught must be a minimum of 12 pascals The insert chamber must con...

Page 7: ...requirements must be complied with with particular reference to the recommendations of Approved Document J The appliance must be installed on a floor with an adequate load bearing capacity If an exist...

Page 8: ...0 DS 14kW 79 150kg 200mm Wood 5 3kg 80mm 45mins Tempo 80 8kW 79 140kg 150mm Wood 3 3kg 80mm 48mins Tempo 70i DS 12 7kW 82 120kg 200mm Wood 3 5kg 80mm 41mins Tempo 70i 4 9kW 76 85kg 150mm Wood 2 5kg 80...

Page 9: ...ng a fire 1 Primary and secondary controls should be fully open If the flue pipe has a flue damper it should also be fully open 2 Remove enough ash from the grate on 80 and 100 models to let air throu...

Page 10: ...sed position To achieve a slow combustion the primary air control must be fully closed and the secondary air control lever must be opened 14mm from the fully closed position or to the DEFRA kit stop i...

Page 11: ...ch ash is not accumulated otherwise there is the danger that if the ash reaches up to the grate it will not cool sufficiently and may get damaged Before emptying the ashpan check if there are any embe...

Page 12: ...is important to have the chimney regularly checked and cleaned by a qualified chimney sweep 5 51 Sweeping single sided versions Remove fire grate Push the back of the throat baffle up so that the baf...

Page 13: ...You now have access for sweeping Repeat each step in reverse to replace all of the parts for normal use 5 52 Sweeping double sided versions Carefully lift the throat plate up off of the retainers pus...

Page 14: ...e can occur due to the accumulation of deposits inside the chimney Immediately close all air regulators on the stove and call the fire brigade If a chimney fire was to occur an experienced professiona...

Page 15: ...f wood Insufficient chimney draught consult installer Glass blackens up Wood has too high a moisture content Secondary air closed down too far Slow burning periods too long Fire won t turn down Wood p...

Page 16: ...ompanying the device Furthermore OPUS declines all liability deriving from improper use of the product by the user including heat shock overload or misuse of the firebox unauthorised modifications and...

Page 17: ...2 12 7 8 14 9 28 15 3 Nominal Heat Output to Water kW N a n a n a n a n a n a n a Net Efficiency 81 76 3 82 70 65 79 78 79 Energy Efficiency Index 107 104 108 103 104 103 104 16 Supplier s Name or Tra...

Page 18: ...80i DS ssss w 14 0 kW ENERGIA EHEPrlllR ENEPrEIA ENERGIJA ENERGY ENERGIE ENERGI 2015 1186 EN ERG oe eHepr111R EVEPVEIO O0 Opus Tempo 100 DS l0Oi DS ssss w 15 3 kW ENERGIA EHEPrlllR ENEPrEIA ENERGIJA...

Page 19: ...his code of practice The appliance and chimney can be fully cleaned once the installation is complete Components for weatherproofing are installed correctly Smoke spillage test has been carried out CO...

Reviews: