PLAN VIEW
SIDE VIEW
Minimum 10mm
Minimum 5mm
When the stove is out keep the air regulators closed, in order for cold air not to be able to
circulate throughout the chimney. However it can be advantageous to open the door some
while before lighting the stove to allow warmer air to begin going up the chimney.
3. Installation of the Stove
The building work must be finished in such a way that the Tempo insert can expand during
operation: the brickwork must never be supported on or against the sides of the appliance.
Leave a minimum expansion joint of 5mm on each side and at least 10mm above the front
3.1 Flue pipe connection
The stove will not burn correctly and efficiently unless it is connected to a properly working
chimney.
The chimney draught must be a minimum of 12 pascals.
The insert chamber must contain no combustible material.
The flue must be fitted in such a way that it cannot be accidentally dislodged during
sweeping.
It is recommended to vent the chamber in which the insert is being installed.
Recommendations:
Minimum chimney height: 4.5 meters
Maximum chimney diameter:
o
Tempo 60, 70 and 80
160mm
o
Tempo 100
220mm
An existing masonry chimney should be lined with an insulated flexible liner
All flue pipe that is used to connect the stove to the chimney must comply with national
regulations.
All connections from the stove into the chimney must be firm, tightly connected and
overlap at least 25mm.