![OptoLum StreamLine Instructions Manual Download Page 3](http://html.mh-extra.com/html/optolum/streamline/streamline_instructions-manual_1644060003.webp)
3 |
S t r e a m L i n e 2 0 1 7
PLAN THE INSTALLATION
The nature and complexity of StreamLine Luminaires installation requires in-depth planning to ensure
timely, successful installation with minimal complications and down time. When planning StreamLine
Luminaire installation, OptoLum suggests doing the following:
Consult an Electrical Inspector to approve all wiring plans
Refer to local and state codes for installation compliance
Contact OptoLum Technical Support Services for troubleshooting
INSTALLATION CONSIDERATIONS
When creating your installation plan, consider the following:
Zones: Create luminaire zones by laying out where the fixtures will be installed that will be
designated to a power supply. All fixtures attached to that power supply reside within the
designated zone. Each zone must not exceed the recommended load on its designated power
supply (See Luminaire Length Table). For installations where groups of luminaires are
controlled individually, set unique zones each with their own power supply.
Location of power supply in relationship to luminaires: Ensure that the appropriate wire
gauge is used to support the distance from the power supply to the luminaire to avoid voltage
drop. Voltage drop will cause damage to the luminaire.
Location of the fixture and method of attaching: Fixture locations need to be determined
to mark mounting clip locations. StreamLine Luminaires are supplied with plastic clips that
are to be attached by inserting a #4 pan head screw (not included) through the hole in the
base of the mounting clip and securing it to a mounting surface such as metal, wood, or
plastic. When the location has been determined, the hole location in the base of the clip
should be marked to indicate predrilling locations for screw installation. Use a level, or chalk
line, to ensure that the hole locations are in line. The mounting clips provided are to be
installed to the mounting surface approximately every 6-8 inches (300mm). In the case of a 6-
12 inch (300mm) fixture the mounting clips should be installed to the mounting surface two
inches (50mm) in from both ends of the fixture to ensure a strong installation. Fixtures
supplied with foam tape or magnetic strip mounting may disregard this consideration, but
should still use a level or chalk line to ensure proper fixture placement.
Luminaire:
StreamLine HO
StreamLine LO
Watt/Foot; (Watt/Meter):
7.9 W/ft (25.9 W/m)
3.5 W/ft (11.5 W/m)
Max Length / 96 Watt Supply:
12 ft (3.65 m)
27 ft (8.23 m)
Max Supply Lead Length (18Ga Wire):
25 ft (7.62 m)
12 ft (3.66 m)
Max Supply Lead Length (16Ga Wire):
40 ft (12.2 m)
19 ft (5.79 m)
Mounting Clip/Foam Tape Table
Minimum required quantity of mounting clips / foam tape segments
Fixture Length
Minimum Quantity Required
up to 6”
1
6" - 12"
2
12" - 24"
3
24" - 36"
4
36" - 48"
5
48" - 60"
6