QUICK START
4
SNAP PID Module User’s Guide
Determining Firmware Version
1.
On the PC, choose Start
➞
Programs
➞
Opto 22
➞
SNAP Ultimate
I/O
➞
ioManager
➞
ioManager.
The ioManager window opens.
2.
Select Inspect from the Mode menu.
The Inspect window opens
3.
Type the IP address of the brain in the field at the upper-left corner of the window and then
click the Status Read button.
4.
Click Status Read in the Ethernet I/O Menu.
5.
Scroll down until you see Kernel Version.
The kernel should be version 3.0.2.0 or higher.
Install the Module
SNAP-PID-V modules can be installed in any position on an Opto 22 B-series mounting rack. Do
not install more than twelve SNAP-PID-V modules on the same rack.
NOTE: SNAP PID modules draw considerably more power than a standard SNAP analog or digital
module. A SNAP-B16M, SNAP-B16MC, or SNAP-B16MC-P rack can handle a maximum of twelve
SNAP PID modules, plus the Ethernet brain and up to four other digital or analog modules. For
detailed power requirements, see the SNAP-PID-V module specifications on
you have sufficient power for the brain and all modules on the rack.
1.
Remove the module from its
packaging.
2.
Position the module over the
connector on the rack, aligning the
small slot at the base of the
module with the retention bar on
the rack. If it is next to another
module, make sure the male and
female module keys are aligned,
as shown at right.
3.
Push straight down on the module
to snap it into position.
If you need to remove the module,
see
.