Mounting the Extrusion onto a Panel

NOTE: If you are not using hold-down screws, the SNAP PAC 
rack assembly should be mounted horizontally. 

Use the following steps to mount a rack onto a panel. For DIN-
rail mounting, see form #1772, the 

SNAP TEX Mounting/Wiring 

and Spare Parts Data Sheet

.

Preferred Method: Template

(Product on site)

1.

Use SNAP PAC rack mounting extrusion as template.

2.

Use the diagram below to determine required product 
and option clearances.

Alternate Method: Prefabrication of Panels

(No product on site)

Mounting holes are in sets of two, located on lower left and 
upper right with respect to a center line (CL).

1.

Using the diagram below, determine CL1 mounting hole 
positions. (CL1 is located on the left side of all SNAP PAC 
rack mounting extrusions.) 

2.

Use the center-to-center length specification table 
below to determine the offset between center lines and 
the number of center line positions for each model.

3.

Repeat the process for each center line position.

Typical Plain View of SNAP Mounting Extrusion

Center-to-Center Length (All Models)

Part Number

Description

Center-to-Center 

Length

Number of Center 

Positions

SNAP-PAC-RCK4 (or -FM)

4-module rack

4.02 in.

2

SNAP-PAC-RCK8 (or -FM)

8-module rack

3.51 in.

3

SNAP-PAC-RCK12 (or -FM)

12-module rack

5.01 in.

3

SNAP-PAC-RCK16 (or -FM)

16-module rack

4.34 in.

4