5.5
Remote Control
The Inverter can be set for daily shutdown/wake up. This command must be set through
the RS-232 interface. When this function is set, the timer inside the Inverter will start, and
the load will be turned OFF according to the shutdown / wake-up schedule. During the
period between a Turn-OFF and a next Turn-ON, the status LED would blink red every 2
seconds. If your Inverter has an LCD display, the time duration to the next Turn-ON will be
shown on the LCD screen measured in hours (Refer to item 15 of the LCD description).
5.6
Reset the Inverter
If any abnormal condition occurs, and the actions described in the paragraphs 4.1~4.7
cannot be executed, please unplug the AC input power cord and push the ON/OFF button
for at least 15 seconds. This will reset the Inverter.
5.7
DIP Switch Settings
Two options: one is for setting the charger parameters, and the
other is for setting the system’s nominal voltage and frequency,
which can also be adjusted using the UPS Wizard or LCD display.
DIP 1
DIP 2
Charging current
NOTE of Charging current control:
The setting of DIP 1 & 2 is valid only when the DIP3 = Down,
which also means that the charger (built in the main PCB) is ON
so that the charging current is adjustable, 25%~100%. While if
the DIP3 = Up, it means that the built-in charger is OFF.
Up
Up
35%
Down
Up
55%
Up
Down
75%
Down
Down
100%
DIP 3 = Down, built-in charger is turned ON; DIP 3 = Up, built-in charger is turned OFF.
DIP 4 is for the Green Mode setting:
UP = Enabled; Down = Disabled
The setting becomes active only after the inverter is restarted.