background image

 

 

www.opti-solar.com 

14 

 

 

No. 

Symbol 

Indication 

Description 

 

Overload 

The total load of the equipment connected to the Inverter exceeds the 

rating of Inverter. 

 

Load level 

The higher the load, the more bars illuminate. 

 

Inverter is 
loaded 

When the “Green Mode” is enabled, this symbol is displayed when the 

load is over a preset level (adjustable, default is 0% = disabled), and 

disappears when the load is under a preset level. Please refer to the 
paragraph 4.9.5. When the “Green Mode” is disabled, the symbol is 

always displayed. 

 

Normal 
mode 

1) The sine wave symbol will display steadily without battery symbol 

when the Inverter is in the normal mode. 

 

Battery 
mode 

2) The sine wave symbol and battery symbol will blink when the Inverter 
is in on-battery (inverter) mode. 

 

Test mode 

3) The sine wave symbol will display steadily with blinking battery 

symbol when the Inverter is in the test mode. 

 

 

Buck mode 

The AVR (Auto Voltage Regulator) is reducing the output voltage of the 

Inverter (when the input voltage is too high), and the sine wave symbol, 
as mentioned in item 4, is also displayed steadily to indicate that the 

Inverter is in the normal mode. 

 

 

Boost mode 

The AVR is increasing the output voltage of the Inverter (when the input 
voltage is too low), and the sine wave symbol, as mentioned in item 4, is 

displayed to indicate that the Inverter is in the normal mode. 

 

Timer is 
enabled 

This symbol will show up in the following situations: 
1) A Turn-ON / Turn-OFF schedule has been set using the monitoring 

software. Refer to paragraph 5.5 and the “Readme” file or “Help” 
function of the monitoring software. 
2) The Green Mode is enabled and the load is under a preset level. The 

Inverter will turn OFF automatically in 60 seconds. Refer to the 
paragraph 4.9.5 of this User’s Manual. 

HIGH

 

Thermal 
alarm 

The temperature inside the transformer is over 90˚C. If the user does 
not reduce the load, the temperature will continue to rise and the 

inverter will shut down automatically after reaching 95˚C. 

 

Fan is at 
“High speed” 

The symbol will display whenever the cooling fan is running at high 

speed, and will disappear when it is off (or running at low speed). 

10 

 

Silence mode 

The audible alarm has been silenced. To reset the alarm while in on-

battery mode, push the control button (not available when the battery 
is low or if Inverter abnormal condition is detected). 

11 

 

Inverter fault 

The Inverter has failed and must be repaired. Contact a qualified service 

person. 

12 

 

Battery 
normal 

1) In normal operation, this symbol indicates a charged battery. 

 

Battery low 

2) When the battery charge level is low, the word “LOW” will be added 

to the symbol. 

13 

 

Battery re-
placement 
required 

The battery has failed and must be replaced. The battery is checked 

each time the Test Function is executed. 

14 

 

Battery 
charge level 

1) The higher the battery voltage, the more bars will illuminate. 

2) When the Inverter is charging the battery, the battery symbol and the 
level indicator blink together. 

 

LOW 

Summary of Contents for SP4000-AVR

Page 1: ...Inverter UPS Hybrid Inverter series User s Manual Sine Wave Output SP4000 AVR www opti solar com...

Page 2: ...e tools with insulated handles To increase the balance of the inverter the additional stabilizer is to be mounted at the bottom side This unit should be installed by qualified personnel The equipment...

Page 3: ...near liquids or in an excessively damp environment Do not let foreign objects penetrate the inverter Never block the ventilation grates of the inverter Never expose the inverter to direct sunlight or...

Page 4: ...ated warning should be observed CAUTION REFER TO USER S MANUAL Refer to this user s manual for additional information such as important operation and maintenance information SAFETY GROUNDING TERMINAL...

Page 5: ...2 3 Description of the Rear panel 8 3 INSTALLATION 9 4 OPERATION 10 5 INDICATION AND CONTROL 13 5 1 LED Display 13 5 2 LCD Display 13 5 3 Audible alarms 15 5 4 Auto Self test Function 15 5 5 Remote C...

Page 6: ...condition With outstanding performance and reliability the unique benefits of the inverter include the following Pure sine wave output Microprocessor based design with true Line Interactive structure...

Page 7: ...same control method Please refer to the following example LEDs of battery voltage level and load level LED of operation status Control Button 2 2 LCD display models The following is one example of LCD...

Page 8: ...utput Terminal and or Outlet s NEMA or IEC 4 RS 232 Interface port for applications with optional monitoring software 5 DIP Switch 6 RJ 45 Interface for a Remote LCD display Optional 7 Battery connect...

Page 9: ...specifications 3 3 Connect the DC input power cord to the battery bank Mind the battery bank s voltage and the polarity The inverter must be as close as possible to the battery bank to avoid the volt...

Page 10: ...the power 4 4 Auto Bypass When the auto bypass function is enabled the Inverter will transfer to by pass mode any time when the inverter is turned OFF It prevents the important connected equipment fr...

Page 11: ...ars on the LCD screen Then push two selection buttons at the same time to change to the next setting or leave the LCD blinking for 30 seconds to finish setting the Inverter and to return to the normal...

Page 12: ...to 1 of full load The inverter will turn OFF the power automatically after a blackout occurs if the load level is less than 1 of the rated full load Push the selection button for 2 seconds at least t...

Page 13: ...e lighted in normal mode the battery is fully charged The load level LEDs show the percentage of added load in relation to the Inverter s rated capacity When all five LEDs are lighted the Inverter is...

Page 14: ...This symbol will show up in the following situations 1 A Turn ON Turn OFF schedule has been set using the monitoring software Refer to paragraph 5 5 and the Readme file or Help function of the monitor...

Page 15: ...a sound alarm When in on battery mode the Utility Failure alarm can be silenced by pushing the Silence button However the Battery Low warning cannot be muted Basic Indication Table STATUS ALARM REMAR...

Page 16: ...ted please unplug the AC input power cord and push the ON OFF button for at least 15 seconds This will reset the Inverter 5 7 DIP Switch Settings Two options one is for setting the charger parameters...

Page 17: ...6 RS 232 data Tx out Pin 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In 6 2 The definition and setup for DB9 optional is shown as follows Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 Pin 5 P...

Page 18: ...vide expected on battery run time 1 Excessive load is connected to Inverter s outlets 2 Battery is weak and cannot provide enough capacity Do not operate the Inverter leave the Inverter plugged in for...

Page 19: ...sfer Time Blackout 3ms typical Over and under voltages 1ms typical Battery mode to Normal mode 1ms typical Overcurrent Protection Overload alarm level 100 120 Overload shutdown level 120 190 Adjustabl...

Page 20: ...rt RJ45 Surge protection DB9 SNMP external type Control Panel LCD Audible Alarms Alarm on battery Low battery Battery over voltage Alarm on abnormal operation Overload Short circuit Overheat Green Mod...