25
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL
3KVA
5KVA
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
120Vac or 230Vac
Low Loss Voltage
95Vac±7V or 170Vac±7V (UPS)
65Vac±7V or 90Vac±7V (Appliances)
Low Loss Return Voltage
100Vac±7V or 180Vac±7V (UPS);
70Vac±7V or 100Vac±7V (Appliances)
High Loss Voltage
140Vac±7V or 280Vac±7V
High Loss Return Voltage
135Vac±7V or 270Vac±7V
Max AC Input Voltage
150Vac or 300Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Loss Frequency
40±1Hz
Low Loss Return Frequency
42±1Hz
High Loss Frequency
65±1Hz
High Loss Return Frequency
63±1Hz
Output Short Circuit Protection
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)
>95% ( Rated R load, battery full charged )
Transfer Time
10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 170V,
the output power will be derated.
Input Voltage
Output Power
Rated Power
50% Power
90V
170V
280V