background image

RANGE SETTING USING THE AUDIO WALK-TESTER OPM-WT

The OPM-WT converts the voltage fluctuations at the detector into a changing audio tone. The tone pitch rises 
and falls as a zone is crossed. When the unit trips into alarm, the tone pitch suddenly rises. If there is no further 
movement the unit will re-set after some 10 seconds and the tone drop back to a lower pitch.

The OPM-WT has a switch allowing selection of either the ‘near’ or ‘far’ detector signals. It is plugged into the 
jack socket on the head underside next to the cable outlet. To avoid confusion, only one channel of the two dual 
channel processors are monitored. This means that crossing the zones one way may give a fluctuating tone 
followed by a trip, whereas crossing in the other direction may give a trip first.

Where the control unit is located close to the detector head, both the walk-tester and the alarm LEDs may be 
observed. (See Fig. 7). Where the control unit is remotely located, the walk-tester is the main means to assist 
with alignment.

If the control unit is remotely located and a walk-tester is not available, it is possible to observe the near and far 
alarm conditions by means of a milliamp meter connected in series with the red (+ve) signal cable. It is even 
possible to align the heads without any connection to the control unit by use of a 12volt battery and a milliamp 
meter. Fig. 8 shows this method and the chart shows the current flows to be expected for the various alarm 
conditions.

The above method only shows alarm trip conditions, it cannot show background fluctuations of the sensor 
signals which may be excessive. The OPM-WT walk-tester is strongly recommended since it is easy to hear any 
fluctuations which may be caused by unwanted motion of the sensor or objects within the zones. It also clearly 
shows where the zone boundaries are and where the ultimate range of the zones are.

Fig. 7

CONTROL

UNIT

FAR LED

NEAR LED

POWER ON  

LED

TAMPER  

LED

MEGARED

HEAD

Fig. 8

MEGARED

HEAD

RED

BLUE

12 VOLT

BATTERY

QUIESCENT
‘NEAR’ TRIPPED
‘FAR’ TRIPPED
BOTH TRIPPED

7.5 mA

19 mA
31 mA
42 mA

MILLIAMPS

OPM-WT

OPM-WT

Summary of Contents for Redwall LRP 180QH

Page 1: ...two outputs may be used to direct an operator to a speci c area of interest or to activate local oodlighting The LRP 180QH comprises two units the detector head and the control unit which contains th...

Page 2: ...is free from damage and that no loose objects are rattling around inside When planning the location remember that all PIR detectors respond best when the intruder crosses the zones IF THE GROUND IS NO...

Page 3: ...150M 250M 150M 300M 500M 850M LRP 180QH DETECTOR MAX RES 20 OHMS 10 OHMS PER CONDUCTOR MR 240 CONTROL RELAYS 12V NOM SUPPLY 11 16V DC IMPORTANT IF ALL CABLES ARE AT MAX PERMITTED RESISTANCE ENSURE TH...

Page 4: ...shunt diode across the input terminals and the reverse connection will blow the power supply fuse if tted or may damage the control unit if not tted With power applied check that the voltage at the su...

Page 5: ...ated the walk tester is the main means to assist with alignment If the control unit is remotely located and a walk tester is not available it is possible to observe the near and far alarm conditions b...

Page 6: ...e Carefully tighten the two tilt bolts and lightly lock the range screw with the locknut THEN RE TEST AT MAXIMUM RANGE TO ENSURE THAT THE HEAD HAS NOT MOVED Reverse the walk test procedure by crossing...

Page 7: ...o Walk tester for Mege Red and REDWAVE LRP Mega Hood Sun Snow Hood LRP Mega Guard Cage 6 8 173 mm 5 5 140 mm 11 0 280 mm 8 8 223 mm 3 15 80 mm 2 38 60 mm MEGARED HEAD CONTROL UNIT 2 3 58 mm 4 9 125 mm...

Page 8: ...770 Fax 909 628 5560 URL http www optexamerica com OPTEX SECURITY SAS FRANCE 475 Rue Piani 69780 Amberieux d Azergues France Tel 33 4 37 55 50 50 Fax 33 4 37 55 50 59 http www optex security com OPTEX...

Reviews: