Fire Protection  |  Data sheet No. 40105  | Version 08-2020  | 

3

3

SOC-E3N Optical smoke detector with YBN-R/6 socket

Oppermann Regelgeräte GmbH

  |  Im Spitzhau 1  |  70771 Leinfelden-Echterdingen, Germany 

Phone +49 711 72723560  |  Fax +49 711 7280527  | [email protected]  | www.oprg.de

Function check

The detector must be tested after installation and at least once 
annually with suitable test spray (e.g. ASR-A10). The red LED 
must light up; the control unit must switch to „Alarm“ and lock 
out. The device is unlocked with the reset button on the  
ABAV-S3 control unit or with a brief power supply interruption.

Maintenance

Contamination of the detector increases alarm sensitivity, which 
can result in false alarms. This can be avoided by cleaning the 
detector as soon as the red contamination indicator LED flashes. 
Cleaning is possible by manufacturer only. The detector must be 
replaced if it is completely contaminated.