background image

Combination detector - presence and brightness OPP-PIR-LUX-1

2

 | 

2

  |  Sensor ventilation air conditioning  |  Data sheet No. 15604  |  Version 02-2012   

Specifications subject to change. 

Oppermann Regelgeräte GmbH

  |  Im Spitzhau 1  |  70771 Leinfelden-Echterdingen, Germany 

Phone +49 711 72723560  |  Fax +49 711 7280527  | [email protected] | www.oppermann-regelgeraete.de

Ø110 mm

Contacts are shown disconnected from power. 
The relay is energized on motion. Contact C - NO is then 
closed. If the brightness drops below the programmed 
threshold and motion is detected, the TTL output is swit-
ched to active (5 V).

Installation

All work (such as installation, electrical connection, startup, 
operation, and maintenance) must only be performed by 
sufficiently qualified tradesmen. The respectively applicable 
local rules and regulations (e.g. national building codes, 
electrical/VDE regulations, etc.) must be observed. Installers 
and operating entities are required to sufficiently familiarize 
themselves before startup. Read the product description 
before operating the equipment. Verify that the product can 
be used for the relevant application without restrictions. We 
are not liable for printing errors and changes after printing. 
Appropriate use implies compliance with operating and 
installation instructions. We are not liable for losses due to 
inappropriate use. Unauthorized or inappropriate manipulati-
ons or modifications of the device render the operating 
permit, the product warranty and warranty claims null and 
void.  

Do not expose the sensor to direct sun irradiation or high 
heat. Do not obstruct the detection zone with flowers, 
furniture, or other objects.

1.  Cut a Ø 60 mm hole into the ceiling. 
2.  Open front cover by loosening the cover screw. 
3.  Now connect the cables and mount the detector to the 

ceiling with screws and dowels.

4.  Verify that both rotating switches are set correctly. Finally, 

position and secure the front cover with screws.

Connecting diagram

Function check

Set ON and OFF lag to 0. Turn on the power supply to the 
detector. Wait 30 seconds to complete the warmup phase. 
Enter the detection space and walk around at normal speed. 
The red LED lights up as soon as the sensor detects motion; 
the relay is energized. If the brightness drops below the 
programmed threshold and motion is detected concurrently, 
the TTL output is switched to 5 V. Appropriately adjust the 
brightness threshold as required with the potentiometer (see 
figure below).

Attention:

Note the arrow (notch) on the rotating switches 
(SW) for the lag. *Default setting ON+OFF: SW = 0; 
only adjust the lag when power has been 
disconnected!!

SW 0*

1

2

3

4

5

6

7

ON 0 seconds

10 

Sec.

20

 Sec.

30

 Sec.

1

 Min.

2

 Min.

5

 Min.

10

 Min.

OFF 10

 Sec.

30

 Sec.

1

 Min.

3

 Min.

6

 Min.

10

 Min.

20

 Min.

30

 Min.

OFF = 

switch-off lag

ON =  

switch-on lag

Red LED

PIR infrared sensor 

(do not touch)

Photocell  

(Don't touch)

Brightness setting

58 mm

27 mm

60 mm

 

SW

4

Circuit board view

Dimensions