background image

onset

®

 

POWER MONITORING 

INSTALLATION GUIDE

 

14724-D 

PAGE 1 

© 2011–2013 Veris Industries and Onset Computer Corporation  

 

Veris and the Veris “V” logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.  

Onset, HOBO, HOBOware, and HOBOlink are trademarks or registered trademarks of Onset Computer Corporation. 

T-VER-E50B2 

 

 

  

  

 

 

 

FCC PART 15 INFORMATION 
Note: This equipment has been tested by the manufacturer and found to comply with the 

limits for a class B digital device, pursuant to part 15 of the FCC Rules. These limits are 
designed to provide reasonable protection against harmful interference when this 
equipment is operated in a residential environment. This equipment generates, uses, 
and can radiate radio frequency energy and, if not installed and used in accordance with 
the instruction manual, may cause harmful interference to radio communications. 
Operation of this equipment in a residential area may cause harmful interference in 
which case the user will be required to correct the interference at his own expense. 
Modifications to this product without the express authorization of Veris Industries 
nullify this statement. 

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 
environment must control conductive pollution and the possibility of condensation or 
high humidity. Consider the enclosure, the correct use of ventilation, thermal properties 
of the equipment, and the relationship with the environment. Installation category: CAT 
II or CAT III 

Provide a disconnect device to disconnect the meter from the supply source. Place this 
device in close proximity to the equipment and within easy reach of the operator, and 
mark it as the disconnecting device. The disconnecting device shall meet the relevant 
requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In 
the US and Canada, disconnecting fuse holders can be used. Provide overcurrent 
protection and disconnecting device for supply conductors with approved current 
limiting devices suitable for protecting the wiring. If the equipment is used in a manner 
not specified by the manufacturer, the protection provided by the device may be 
impaired. 

 

T-VER-E50B2 

Compact Power and Energy Meter 

Installer’s Specifications 

Measurement Accuracy: 

Real Power and Energy 

IEC 62053-22 Class 0.5S, ANSI C12.20 0.5% 

Reactive Power and Energy 

IEC 62053-23 Class 2, 2% 

Current 

0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range; 

 

0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range 

Voltage 

0.4% (+0.015% per °C deviation from 25°C) from 90V (L-N) to 600VAC (LL) 

Sample Rate 

2520 samples per second 

Data Update Rate 

1 sec 

Type of Measurements 

True RMS up to the 21st harmonic 60 Hz, 

 

One to three phase AC system 

Input Voltage Characteristics: 

Measured AC Voltage 

Minimum 90VL-N (156VL-L) for stated accuracy 

 

UL Maximums: 600V

L-L 

(347V

L-N

 

CE Maximums: 300V

L-N

 (520V

 L-L

Metering Over Range 

+20% 

Impedance 2.5 

M

Ω

 (L-N)/5 M

Ω

 (L-L) 

Frequency Range 

45 to 65 Hz 

Input Current Characteristics: 

CT Scaling 

Primary:  Adjustable from 5 A to 32,000 A 

Measurement Input Range 

0 to 0.333VAC or 0 to 1.0VAC (+20% over-range) 

Impedance 10.6k

Ω

 (1/3 V mode) or 32.1k

Ω

 (1 V mode) 

Control Power: 

AC 

5VA max.; Minimum 90VAC, 

 

UL Maximums: 600V

L-L 

(347V

L-N

), 

 

CE Maximums: 300V

L-N

 (520V

 L-L

DC* 

3W max.; UL and CE: 125 to 300VDC 

Ride Through Time 

100 msec at 120VAC 

Output: 

Maximum Pulse Output 

50 Hz 

Amp Hour 

N.C., static output (30VAC/DC, 100mA max. @ 25°C, 

 

derate 0.56mA per °C above 25°C) 

Real/Reactive Energy 

N.O., static output (30VAC/DC, 100mA max. @ 25°C, 

Pulse Contacts 

derate 0.56mA per °C above 25°C) 

Mechanical Characteristics: 

Weight 

0.62 lb (0.28 kg) 

IP Degree of Protection (IEC 60529) 

IP40 front display; IP20 Meter 

Display Characteristics 

Back-lit blue LCD 

Terminal Block Screw Torque 

0.37 ft·lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) max. 

Terminal Block Wire Size 

26 to 14 AWG (0.13 to 2.08 mm2) 

Rail 

T35 (35mm) DIN Rail per EN50022 

Environmental Conditions: 

Operating Temperature 

-30° to 70°C 

Storage Temperature 

-40° to 85°C 

Humidity Range 

<95% RH (non-condensing) 

Altitude of Operation 

3 km max. 

Metering Category: 

North America 

CAT III; for distribution systems up to 347 V L-N/600VAC L-L 

CE 

CAT III; for distribution systems up to 300 V L-N 

Dielectric Withstand 

Per UL 508, EN61010  

Conducted and Radiated Emissions 

FCC part 15 Class B, EN55011/EN61000 Class B 

 

(residential and light industrial) 

Conducted and Radiated Immunity 

EN61000 Class A (heavy industrial) 

Safety: 

North America (cULus) 

UL508 (open type device)/CSA 22.2 No. 14-05 

Europe (CE) 

EN61010-1:2001 

External DC current limiting is required, see fuse recommendations.

 

 

This symbol indicates an 
electrical shock hazard exists. 

Documentation must be consulted where 
this symbol is used on this product. 

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for T-VER-E50B2

Page 1: ...Measurement Accuracy Real Power and Energy IEC 62053 22 Class 0 5S ANSI C12 20 0 5 Reactive Power and Energy IEC 62053 23 Class 2 2 Current 0 4 0 015 per C deviation from 25 C from 5 to 100 of range...

Page 2: ...e The LCD screen on the faceplate allows instant output viewing The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022 The E50 can be mounted with an...

Page 3: ...the housing and the screw hole must be exposed on the outside of the housing 2 Use three 8 screws not supplied to mount the meter to the back of the enclosure See diagram of the underside of the meter...

Page 4: ...arallel wires for control power and voltage inputs The following symbols are used in the wiring diagrams on the following pages Symbol Description Voltage Disconnect Switch Fuse installer is responsib...

Page 5: ...ation WIRING DIAGRAMS CTs are not polarity sensitive No need to observe orientation Diagram 1 1 Phase Line to Neutral 2 Wire System 1 CT SYSTEM TYPE 1L 1n Diagram 2 1 Phase Line to Line 2 Wire System...

Page 6: ...C to 347 VAC UL or 300VAC CE Direct Connect Control Power DC Control PowerTransformers CPT Connection DC Control Power from 125VDC to 300VDC UL and CE max The Control Power Transformer may be wired L...

Page 7: ...mA 50 C The over current protective device must be rated for the short circuit current at the connection point Pulse outputs are only intended to be connected to non hazardous voltage circuits SELV or...

Page 8: ...SYSTM screen Use or to select the System Type see wiring diagrams on pages 9 10 b back to the S SYS screen 6 Optional to the S PT Set Potential Transformer screen If PTs are not used then skip this st...

Page 9: ...AC VAB VBC VAC Voltage Line to Line V VLN Voltage Line to Neutral PF PF Power Factor U VLL Voltage Line to Line HZ HZ Frequency kSh kVAh Accumulated Apparent Energy kQh kVARh Accumulated Reactive Ener...

Page 10: ...on Veris and the Veris V logo are trademarks or registered trademarks of Veris Industries L L C in the USA and or other countries Onset HOBO HOBOware and HOBOlink are trademarks or registered trademar...

Page 11: ...ris and the Veris V logo are trademarks or registered trademarks of Veris Industries L L C in the USA and or other countries Onset HOBO HOBOware and HOBOlink are trademarks or registered trademarks of...

Page 12: ...poration Veris and the Veris V logo are trademarks or registered trademarks of Veris Industries L L C in the USA and or other countries Onset HOBO HOBOware and HOBOlink are trademarks or registered tr...

Page 13: ...emarks or registered trademarks of Veris Industries L L C in the USA and or other countries Onset HOBO HOBOware and HOBOlink are trademarks or registered trademarks of Onset Computer Corporation USER...

Page 14: ...caling is listed below You can also enter custom scaling values in the following increments in both HOBOware and HOBOlink Refer to the HOBOware or HOBOlink help for more details Reactive Energy VARh 1...

Page 15: ...Usable Pulse Scale Setting for Wh VARh Key 1 Wh per pulse default 10 Wh per pulse 100 Wh per pulse 1 000 Wh per pulse 10 000 Wh per pulse 3 Phase Systems 2 Phase Systems Single Phase Systems Minimum U...

Page 16: ...eris and the Veris V logo are trademarks or registered trademarks of Veris Industries L L C in the USA and or other countries Onset HOBO HOBOware and HOBOlink are trademarks or registered trademarks o...

Reviews: