background image

Section 7: Diagnostics and Troubleshooting 

HOBO Energy Logger User’s Guide 

35 

delayed or interval start, check the date and time you selected and make 
sure the 

Delayed Start 

indicator is blinking. If you configured the logger 

to launch with the 

Trigger 

start option, press and hold the 

Push to Start 

button on the logger until all the indicators flash at once (at least two 
seconds). 

Memory Low (Red) 

If the logger was launched with wrapping disabled, this indicator blinks 
when less than 25% of memory remains for saving data. The logger will 
continue to run until all memory is used.  

If the logger was launched with wrapping enabled, this indicator should 
not blink. 

Battery Low (Red)  

This indicator blinks when battery power is at less than 25% capacity, or 
if the batteries are installed improperly. The logger will continue logging 
until the batteries are dead; however, you should read out the data and 
replace the batteries as soon as possible, before the batteries die, and then 
relaunch the logger. Or, attach an external power source if possible. 

If this indicator continues to blink even after you have replaced the 
batteries: 

 

Check that the batteries are installed properly. If the polarity of 
any of the batteries is incorrect, this indicator will blink.  

 

Make sure you are using the correct battery type. The logger uses 
eight 1.5 volt AA alkaline or lithium batteries. The battery type 
must be specified correctly on the Launch Logger dialog for the 
correct battery status to be reported.  

 

Make sure all batteries are of the same type - either all alkaline, 
all enhanced alkaline, or all lithium. Never mix battery types. 

 

Check the battery expiration date. Verify that the expiration date 
is at least two years from the current date. Batteries can lose 
significant capacity if stored at elevated temperatures. 

 

Check the voltage of the batteries with a voltmeter. Alkaline 
batteries should be at least 1.5 V per cell when new; fresh 
lithium batteries should be 1.6 V per cell. 

Section 7: Diagnostics and Troubleshooting 

36 

 

HOBO Energy Logger User’s Guide 

Sensor Fail (Red) 

This indicator blinks when there is or has been a FlexSmart module or 
Smart Sensor communication failure. 

Note:

 If the 

Sensor Fail 

indicator is blinking, you should read out the 

logger, investigate the problem, and then relaunch the logger.  

 

If the 

Sensor Fail 

indicator is blinking in conjunction with the 

Logging

 indicator, there was a communication failure, but the 

system has recovered. There may be an intermittent problem. 
Try checking the FlexSmart modules and Smart Sensors one at a 
time to make sure they are all communicating. If you find a bad 
module or sensor, or if no module or sensor communicates, 
contact your Onset Authorized Dealer or Onset Technical 
Support. 

 

If the 

Sensor Fail

 indicator is the only one that is blinking, at 

least one FlexSmart module or Smart Sensor is currently not 
communicating. You should investigate this problem 
immediately. Look for a loose connection, which could cause 
bad electrical contact with a module or sensor. If found, remove 
the offending module or sensor and check its wires and 
connector for damage and/or signs of moisture. 

Problems and Solutions 

Problem Solution 

No status 
indicators are 
blinking 

The indicators are very faint under direct sunlight or 
bright fluorescent lighting. If no indicators appear to 
be blinking, shield the logger from the light and 
check the indicators again. 

Check the status in HOBOware: 

 

Make sure the batteries are not dead. 
Batteries should have at least 1 volt per cell.  

 

The memory may be full. Read out the 
logger and relaunch.  

 

The logger may not have been launched.  

w

w

w

.

G

lo

ba

lTe

st

Su

pp

ly

.c

om

Fin

d Q

ua

lit

y P

ro

du

ct

s O

nli

ne

 a

t:

sa

le

s@

G

lo

ba

lTe

st

Su

pp

ly.c

om

Summary of Contents for H22-001

Page 1: ...and lock out all power sources during installation and servicing Please read the user s manual for instructions and use 2009 2017 Onset Computer Corporation All rights reserved Onset HOBO HOBOware and...

Page 2: ...e 19 Configuring Channels on the Analog Module 20 Verifying Operation 20 Sensor Excitation 20 Working with Channels 22 Section 4 Batteries and External Power 23 Selecting batteries 23 iv HOBO Energy L...

Page 3: ...rgy Logger Energy Logger User s Guide Eight 1 5V alkaline batteries One miniature slotted screwdriver Blank label Rubber feet Section 1 Introduction 2 HOBO Energy Logger User s Guide Specifications Op...

Page 4: ...gging begins Automatic detection of Smart Sensors The logger automatically recognizes Smart Sensors No programming wiring or calibration is required to set them up Digital network The connections betw...

Page 5: ...was selected in HOBOware during launch Indicator LEDs There are three green and three red status indicators The green indicators blink to show status or activity The red indicators blink to show that...

Page 6: ...rews Energy Logger Mounting Kit A H22 DINMOUNT 1 Allows you to mount the logger to industry standard 32 mm and 35 mm DIN rails Energy Logger Spares Kit A H22 SPARES Spare bumpers screwdriver and FlexS...

Page 7: ...tch the polarity marked in the battery compartment Refer to Selecting Batteries on page 23 for tips on selecting the right battery type for your application Replace the battery compartment door and ti...

Page 8: ...daptability HOBOware lets you configure these modules at launch time or create and save different configurations to be loaded into the modules whenever needed If you connected only Smart Sensors skip...

Page 9: ...O Energy Logger User s Guide Depending on the option you select the logger may start automatically either immediately or at a specified time or you may start it manually by pressing the Push to Start...

Page 10: ...elect a minimum 2 second logging interval If all TRMS modules are configured for single channel use you can use a 1 second logging interval 4 If you are using sensor excitation configure it for each F...

Page 11: ...stop the logger read it out swap the sensors and then relaunch Smart Sensor Cables The logger can work with a maximum total of Smart Sensor cable lengths up to 100 meters 328 feet as measured from th...

Page 12: ...cept a wide range of sensors That means that each channel can be configured to measure either current or voltage and the collected data can be scaled to produce meaningful results that are consistent...

Page 13: ...ogger s internal battery channel at launch If the battery becomes too low to provide excitation power excitation power is turned off but logging continues as long as the battery can power the logger T...

Page 14: ...For low current applications however they offer little improvement Section 4 Batteries and External Power 24 HOBO Energy Logger User s Guide Battery type Considerations for use Lithium Li FeS2 Lithium...

Page 15: ...Voltage Input Adapter S VIA CM14 Photosynthetically Active Radiation PAR S LIA M003 Silicon Pyranometer Solar Radiation S LIB M003 Note Although some Smart Sensors are intended mainly for outdoor use...

Page 16: ...Energy Logger User s Guide logger contact the vendor that sold it to you It may be possible to retrieve the logged data External Power Sources An external power source can reduce or eliminate the need...

Page 17: ...is scheduled for an extended deployment Verify logger operation Before each deployment Section 5 Maintenance 30 HOBO Energy Logger User s Guide Inspecting the Logger Housing and Cables Periodically p...

Page 18: ...ogger may lose up to two seconds when it is launched This is a one time error that occurs as part of the start up sequence and cannot be avoided Clock drift The logger s long term time accuracy is rel...

Page 19: ...ostics and Troubleshooting 34 HOBO Energy Logger User s Guide Section 7 Diagnostics and Troubleshooting This section lists some symptoms and tips to help you confirm correct operation of your logger a...

Page 20: ...significant capacity if stored at elevated temperatures Check the voltage of the batteries with a voltmeter Alkaline batteries should be at least 1 5 V per cell when new fresh lithium batteries shoul...

Page 21: ...both the logging and sampling intervals are set for at least one minute or greater Fast sampling and logging intervals shorter than one minute will rapidly deplete the battery For more information re...

Page 22: ...0 34 36 36 Logging interval 2 15 17 20 21 24 33 37 Measurement averaging See Sampling interval Memory 2 14 27 33 36 wrapping 13 14 35 Power adapter power supply see External power source Sampling inte...

Reviews: