background image

NEOS-HSD200 

User Manual

 

 

 

Revision 1.00 

Summary of Contents for NEOS-HSD200

Page 1: ...NEOS HSD200 User Manual Revision 1 00...

Page 2: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 2 Revision Information Release of NEOS HSD200 User Manual is as below Revision Date Description 1 00 2022 01 01 Initial Production...

Page 3: ...ication Method 24 5 1 2 Communication Frame 24 5 1 3 Data Request 24 5 1 4 Alarm Reset 26 5 1 5 Temperature Warning Alarm Threshold Setting 26 5 1 6 Deviation Reference Value Setting 27 5 1 7 Temperat...

Page 4: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 4 How to Install 40 6 1 Startup and Setup 40 Others 41 7 1 How to Reset 41 7 2 How to Use Monitoring Program 42...

Page 5: ...semble process improve or repair this device There is a risk of abnormal operation electric shock or fire When detaching this device turn off the power before taking action It may cause electric shock...

Page 6: ...such as temperature warning and alarm standard values can be changed Dual RS485 communication port provides convenience for communication cable wiring Convenience of communication interface provided b...

Page 7: ...ssible in one product so it is expected to have a drastic cost reduction effect 2 In the case of the existing case when designing the entire length of the panel the temperature probe temperature contr...

Page 8: ...mmunication 5 Reset button Smoke detection and temperature alarm reset 6 Setting Button Change detector settings 7 Status LED Detector status indication 8 Temperature Humidity sensor Temperature and h...

Page 9: ...el 1 5 Level 2 10 Level 3 15 Temp 40 125 Humi 0 100 RH Resolution Temp 0 1 Humi 0 1 RH Accuracy Temp 0 4 Humi 3 0 RH Operating temperature 20 70 0 95 RH Non condensing Storage temperature 30 85 0 95 R...

Page 10: ...UT2 Smoke detection RLY N O 2 DOUT4 Temperature warning 3 DOUT6 Temperature alarm RLY N C 4 IN COM Remote rest Common 5 DOUT COM NPN output Common 6 N 24V Power GND 7 DOUT1 Running 8 DOUT3 Smoke detec...

Page 11: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 11 RS485 Connector 1 2 No Name Description Remarks 1 RS485 B RS485 TRXD 2 RS485 GND RS485 GND 3 RS485 A RS485 TRXD 4 FG Frame Ground...

Page 12: ...r is supplied It is recommended to use the same pair of cables as the UL2919 series It supports connection of up to 32 units 2 Relay Output Since it is an output of 1A1B contact type the host controll...

Page 13: ...FFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 13 8 DOUT3 Smoke detect RLY N C 1 DOUT2 Smoke detect RLY N O 3 DOUT6 Smoke detect RLY N O 9 DOUT5 Smoke detect RLY N O 11 RLY Com Relay...

Page 14: ...pe digital output signal it provides the running status of the product and the output of the temperature warning signal 4 NPN Type Digital Input Receives NPN type digital input signal to perform remot...

Page 15: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 15 2 5 Dimensions Outline Drawing Dimension D Panel Mounting Position M4 Bolt Assembly 3 places...

Page 16: ...ith the FRONT direction marked on the bracket facing the front display direction Align the positions of the grooves marked on the front of the bracket with the grooves on the product and align the pro...

Page 17: ...and Smoke detector NEOS HSD200 User Manual 17 Components Heat and Smoke Detector NEOS HSD200 1pcs 43025 0400 _ MOLEX 4PIN Housing 2pcs 43030 0001 _ MOLEX Pin Terminal 20pcs 43025 1200 _ MOLEX 12PIN Ho...

Page 18: ...rning 3 Temperature alarm 4 Detector ERROR 5 1 Displays the current temperature and humidity status 2 Displays the status when smoke is detected 3 When a temperature warning occurs the status is displ...

Page 19: ...otocol setting 10 END code setting 11 Display sleep setting 12 9 Displays RS 485 communication speed information 10 Displays protocol setting information 11 Displays End Code setting information 12 In...

Page 20: ...ase reset Temp decrease reset Temp warning value setting Temp warning deviation value Temp alarm value setting ID number setting Enable temp warnings and alarms Temp warning hold setting Temp alarm gl...

Page 21: ...peration Details of the Setting Screen 1 Change the temperature warning value and change the temperature warning deviation value Change the temp warning and deviation values to one decimal point MODE...

Page 22: ...xt setting screen when pressed once If pressed for 3 seconds it moves to the main screen after setting the current value UP Change Usage status DISABLE to ENABLE DOWN Change Usage status ENABLE to DIS...

Page 23: ...g output type MODE Move to the next setting screen when pressed once If pressed for 3 seconds it moves to the main screen after setting the current value UP Change the output TYPE from A_TPYE to B_TYP...

Page 24: ...NOFF protocol communication packet and sent 10 Set display auto off Change the use of auto off of the display MODE Move to the next setting screen when pressed once If pressed for 3 seconds it moves t...

Page 25: ...o the main screen after setting the current value UP Change in order of DISABLE 1MIN 10MIN 30MIN 60MIN DOWN Change in order of 60MIN 30MIN 10MIN 1MIN DISABLE Each time setting is in minutes Setting in...

Page 26: ...seconds it moves to the main screen after setting the current value UP Change in order of LEVEL 1 LEVEL 2 LEVEL 3 DOWN Change in order of LEVEL 3 LEVEL 2 LEVEL 1 LEVEL 1 Smoke detection occurs at smok...

Page 27: ...NEOS HSD200 User Manual 27 16 EXIT Exit the setting screen without changing the setting value MODE Move to the next setting screen when pressed once When pressed for 3 seconds it moves to the main sc...

Page 28: ...STX 0x53 1 Byte ETX 0x45 1 Byte 3 Length Number of bytes from CMD to DATA ex 0x0014 in case of 20 Byte 4 CMD Communication command 5 Code Command division 6 Count Transmission Count repeat 0 255 7 DAT...

Page 29: ...fer value MSB LSB HEX 0x10 0xD6 INT 4310 Input value 43 1 Data MSB Description LSB Description Bit 0 0 Display Slip not used Running 1 Use Display Slip Stop Bit 1 0 Buzzer not used Smoke detection 1 U...

Page 30: ...d Setting 1 PC Sensor Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Format STX Length MSB LSB CMD MSB LSB Code Count Data ID Error WARNING REFERENCE MSB LSB ALARM REFERENCE MSB LSB HEX 0x53 0x00 0x0C 0x05...

Page 31: ...sor PC Normal command response Index 0 1 2 3 4 5 6 7 8 9 10 11 14 Format STX Length MSB LSB CMD MSB LSB Code Count Data ID Error Deviation refer value MSB LSB HEX 0x53 0x00 0x0C 0x05 0xA3 0x06 0x00 0x...

Page 32: ...when USED is set 5 1 8 Enabling Keep Temperature Alerts 1 PC Sensor Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Format STX Length MSB LSB CMD MSB LSB Code Count Data ID Error Enable warning HEX 0x53 0x0...

Page 33: ...7 8 9 10 11 14 Format STX Length MSB LSB CMD MSB LSB Code Count Data ID Error Enable alarm HEX 0x53 0x00 0x0C 0x05 0xA3 0x05 0x00 0x01 0x00 0x01 0x00 0x00 15 16 17 18 19 Checksum ETX CR LF 0x45 0x0D...

Page 34: ...ld is as follows Fields Description Device Address Device Address is used to identify each slave device and ranges from 1 to 63 Function Code When sending a request from the master to the slave it mea...

Page 35: ...ibed with holding register and data to be recorded Registers are accessed with addresses starting from 16 16 10h Write Multiple Registers Write values to several consecutive registers among holding re...

Page 36: ...ever if more than 30 registers are read an error is sent because overflow occurs in the byte count field 5 Response detailed structure Name Byte Length Description Function Code 1 3 03h Read holding r...

Page 37: ...ue 1 byte 2 bytes 2 bytes 3 Request detailed structure 4 Response detailed structure Name Byte Length Description Function Code 1 6 06h Write Single Register Register Address 2 It is the same as the v...

Page 38: ...ss Quantity of Registers 1 byte 2 bytes 2 bytes 3 Error Response 4 Request detailed structure Name Byte Length Description Function Code 1 16 10h Write Multiple Register Starting Address 2 Holding reg...

Page 39: ...reads Modbus holding register 0 3 using function code 03h Read holding register Register 0 3 is accessed by address 0 3 on the packet Device Address of NEOS HSD200 is assumed to be 1 1 Request Packet...

Page 40: ...OS HSD200 User Manual 40 5 2 7 CRC 16 Modbus Algorithm 1 Create CRC uint16_t CRC16 uint8_t buf size_t len Uint16_t crc 0xffff for int pos 0 pos len pos crc uint16_t buf pos for int i 8 I 0 i if crc 0x...

Page 41: ...0 Unuse 1 Use 2 Smoke Detection Level 00 1Level 01 2Level 10 3Level 3 4 Heartbeat Setting 3bit 000 Unuse 001 1 min 010 10 min 011 30 min 100 1 hour 5 6 7 Reserved Byte L LSB 0 Running ON Operative OFF...

Page 42: ...re 100 Receiver Received value 100 Byte L LSB Reserve Read 40968 A0 08 Word Byte H MSB Reserve Byte L LSB Reserve Read 40970 A0 0A Word Byte H MSB Reserve Byte L LSB Reserve Read 40972 A0 0C Word Byte...

Page 43: ...Byte L LSB 0 Unuse 1 Use Read Write 40984 A0 18 Word Byte H MSB Temperature warning maintenance operation Enable Disable Byte L LSB 0 Normal 1 Maintain Read Write 40986 A0 1A Word Byte H MSB Temperatu...

Page 44: ...le DOWN Disable switch on the setting screen 4 Communication speed setting 1 Change by pressing the UP DOWN switch on the setting screen The default is 115200 and it is changed in the order of 57600 3...

Page 45: ...ary by using the UP DOWN switch 9 Save settings and complete 1 In the SAVE EXIT item press the MODE switch for 3 seconds to save the changed setting value and return to the main screen to complete the...

Page 46: ...RESET After smoke detection alarm After warning occurs in the temperature warning maintenance parameter setting state After an alarm occurs in the temperature alarm maintenance parameter setting state...

Page 47: ...UI program You can check the measurement data by connecting multiple heat and smoke detectors up to 32 at the same time through RS485 communication with a PC Real time smoke detection temperature war...

Page 48: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 48 humidity information can be checked Setting values such as temperature warning and alarm threshold can be changed...

Page 49: ...ature and humidity data of heat and smoke detectors in graphs 5 Log storage function Record log information of heat and smoke detector Start Start saving log information Stop Stop saving log informati...

Page 50: ...duct model name 3 Protocol Select the protocol to connect the communication to 4 End_Code Decide whether to use CR LF in ONOFF protocol 5 Connection port Select currently connected port 6 Communicatio...

Page 51: ...mperature warning maintenance Enable Disable applied 4 Keep Temperature Alarm Enable Disable Temperature alarm maintenance Enable Disable applied 5 Alarm reset command Send alarm reset command 6 Tempe...

Page 52: ...with the scan Progress status Scanning status is displayed while the connected heat smoke detector is being scanned Progress status When the scan is completed click button to start updating heat smok...

Page 53: ...ONOFFSYSTEM Co Ltd Heat and Smoke detector NEOS HSD200 User Manual 53 4 Graph It displays the temperature and humidity data of the selected heat smoke detector ID in a graph...

Page 54: ...quipment Broadcasting and Communication Equipment for Business User s Guide This device has undergone conformity assessment for use in a business environment and there is a risk of radio wave interfer...