SECTION 7.0: MODBUS
MODBUS
®
serial interface connections are connected at terminal block TB4.
Transceiver: 2-wire, half-duplex (1/4 unit load)
MODBUS
®
Address Range: 1 - 247 (Default: 017)
Data Format: 8 bit
Stop Bits: 1
Parity: None (Default), Odd, or Even
Byte Order: ABCD
Baud Rate: 4800, 9600, 19200, 38400, 57600, 76800 or 115200 (Default: 9600)
Termination: Jumper selectable 120
Ω
resistor (See page 13)
Biasing: None
Engineering Units
Abbreviation
Engineering Units
Abbreviation
Volume Rate (Flow)
Volume Total
Gallons per minute
GPM
Gallons
Gal
Liters per second
L/s
Liters
Liters
Cubic feet per minute
fT
3
/min
Cubic Feet
ft
3
Cubic meters per hour
m
3
/hr
Cubic Meters
m
3
Temperature
Degrees Fahrenheit
ºF
Degrees Celsius
ºC
Velocity (Flow velocity, Fluid speed of sound)
Feet per second
ft/s
Meters per second
m/s
Function Codes Supported:
01 - Read Coil(s)
02 - Read Discreet Input(s)
03 - Read Holding Register(s)
04 - Read Input Register(s)
05 - Write Single Coil
06 - Write Single Register
08 - Diagnostic
15 - Write Multiple Coils
16 - Write Multiple Registers
17 - Report Slave ID