5
< SYSMAC-C PLC Setup >
(1) C200H-LK201-V1/LK-202-V1 Setup
1) Set station number.
Station Number is set by SW1 and SW2. SW1 is X10, SW2 is X1.
2) Baud Rate Setting
Set by SW3. Setting values according to SW Set are as follows.
Switch
Baud Rate(bps)
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
3) Command Level Setting
Set by SW4. Recommend 2.
Switch
Command Level
Parity
Etc.
0
Level 1 available
even
ASCII 7bit
2 Stop bit
1
Level 1,2 available
2
Level 1,2,3 available
3
Disable setting
4
Level 1 available
odd
5
Level 1,2 available
6
Level 1,2,3 available
7
Disable setting
8
Level 1 available
even
JIS 8bit
1 Stop bit
9
Level 1,2 available
A
Level 1,2,3 available
B
Disable setting
C
Level 1 available
odd