7 Handling Errors
7 - 6
NA-series Programmable Terminal Soft-NA User’s Manual (V126)
Errors determined with messages
When an object is touched, noth-
ing is input or executed
A communications error
occurred.
Check the connection between the
Soft-NA and connected device.
The
IsEnabled
Check Box is not
selected in the object settings.
Select the
IsEnabled
Check Box in the
object properties on the Sysmac Studio.
Security is set.
If you change the IsEnabled property,
e.g., from a subroutine, set it to True.
Operation is not possible for all
objects
The Soft-NA is in Input Prohibited
Mode.
Use the EnableInputOperation function
or EnableInputOperation action to
enable the inputs that are currently pro-
hibited.
Log in at a level where input is allowed.
It is not possible to move to the
System Menu
The currently logged in user does
not have permission.
Go to the System Menu and log in as a
level that has permission to display the
System Menu.
Output message
Cause
Correction
E_SNA_999
An unexpected error has
occurred.
Restart the Soft-NA.
An unexpected error occurred
during Runtime execution.
Restart the Soft-NA.
E_SNA_001
The project data is corrupted.
Transfer the project data again.
There is a problem in the project
data.
Transfer the project data again from Sys-
mac Studio.
E_SNA_100
The Soft-NA is already running.
The Soft-NA was started when it
was already running.
Exit the running Soft-NA, and then exe-
cute it.
E_SNA_101
An unexpected error has
occurred.
Restart the Soft-NA.
An unexpected error occurred
during Runtime execution.
Restart the Soft-NA.
E_SNA_102
The project data is corrupted.
Transfer the project data again.
There is a problem in the project
data.
Transfer the project data again from Sys-
mac Studio.
E_SNA_103
The project data is corrupted.
Transfer the project data again.
There is a problem in the project
data.
Transfer the project data again from Sys-
mac Studio.
E_SNA_104
Insert the USB dongle for
Soft-NA.
The USB dongle cannot be
accessed from the Soft-NA.
• Insert the USB dongle for the Soft-NA
into the PC.
• Restart the PC.
• Try restarting the Soft-NA after waiting
for around 30 seconds.
E_SNA_105
Insert the USB dongle for
Soft-NA.
The USB dongle cannot be
accessed from the Soft-NA.
• Insert the USB dongle for the Soft-NA
into the PC.
• Restart the PC.
• Try restarting the Soft-NA after waiting
for around 30 seconds.
''Transferring project data to HMI'
failed.
Transfer the project data again.
Failed to transfer the project data. • Assign write permission for <Soft-NA
Installation Drive>\OMRON.
• Again create the project data for trans-
fer in Sysmac Studio.
Soft-NA symptom
Cause
Correction
Summary of Contents for Sysmac NA Series
Page 1: ...Programmable Terminal NA series Soft NA User s Manual V126 E1 01 NA RTLD...
Page 8: ...Sections in this Manual 6 NA series Programmable Terminal Soft NA User s Manual V126...
Page 24: ...Revision History 22 NA series Programmable Terminal Soft NA User s Manual V126...
Page 42: ...3 Startup and Exit 3 8 NA series Programmable Terminal Soft NA User s Manual V126...
Page 78: ...7 Handling Errors 7 8 NA series Programmable Terminal Soft NA User s Manual V126...
Page 82: ...Appendices A 4 NA series Programmable Terminal Soft NA User s Manual V126...
Page 83: ...I 1 I NA series Programmable Terminal Soft NA User s Manual V126 Index...
Page 85: ......