5 Sysmac Studio Settings for the EtherNet/IP Unit
5-6
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
5-4
FTP Settings Display
*1
These settings are required to use the FTP server.
*2
The following ports are used by the system and cannot be set by the user: 9600 and 44818.
*3
The login name and password are case sensitive.
Additional Information
Refer to Section 9 FTP Server for details on the FTP server.
Setting
Description
Default
FTP server
Specify whether to use the FTP server.
FTP connections from external devices will not be possible if the Do not use
Option is selected.
Do not use.
Port No.
*1*2
Set the FTP port number of the EtherNet/IP Unit. It is normally not neces-
sary to change this setting.
The port number that is one less than the specified port number is used for
data transfer.
0 (port No. 21)
Login name
*1
Set the login name to externally connect to the EtherNet/ IP Unit via FTP.
(You can use up to 12 alphanumeric characters.)
*3
None
Password
*1
Set the password to externally connect to the EtherNet/IP Unit via FTP. (You
can use up to 8 alphanumeric characters.)
*3
None
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......