Names of Parts

Main circuit

terminal block

(input side)

Communications

connector

Relay output

terminal block

Control circuit
terminal block

Main circuit

terminal block

(output side)

For factory
maintenance only
Do not touch.

OPE/485 communications
selector(S7)

Emegency shut off 
function selector(S8)

Digital Operator

Installation and Wiring

Ŷ

Dimensions

3G3JX-

W

W1

H

H1

D

A2002, AE002

95.5

A2004, AE004

109.5

A2007

80

67

155

143

132.5

A4004, AE007

130.5

A2015, A2022, A2037,
A4007, A4015, A4022,
A4037, AE015, AE022

110

98

189

176

157.5

A2055, A2075, A4055,
A4075

180

164

250

235

167.5

[mm]

W

W1

H1

H

1.9

D

Regenerative Braking unit

DC reactor

3-phase 200V AC

Single/3-phase 200V AC

3-phase 400V AC

Multi-function input 1

2

3

4

5

Frequency reference
power supply

Frequency
reference

Frequency reference
(current)

Common

M

R/L1 (L1)

+1

P/+2

N/-

T/L3 (N/L3)

S/L2 (L2)

U/T1

W/T3

MB

MA

MC

P1

PC

Multi-function
output

AM

Analog monitor
output

Relay output

V/T2

PSC

P24

S2

S1

S5

SC

FS

FI 

FC

FV

S4

S3

*1. Connect a single-phase 200V AC input to terminals L1 and N/L3.
*2. Factory default settings for relay output are NC contact for MA and NO contact for MB.

Ŷ

Terminal symbols, Screw size and Tightening Torque

Main

circuit

R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
Ground(symbol)

Option

N/-, P/+2, +1

M3.5

0.8N·m

(max.0.9N·m)

M4

1.2N·m

(max.1.3N·m)

M5

3.0N·m

(max.3.3N·m)

Control
circuit

AM, FS, FV, FI,

FC, S5, S4, S3,

S2, S1, SC, PSC,

P24, PC, P1

Relay

MA, MB, MC

Ground

M4

M5

Type

Terminal
symbol

A2002 ~ A2007
AE002 ~ AE004

A2015 ~ A2037
A4004 ~ A4037
AE007 ~ AE022

A2055 ~ A2075
A4055 ~ A4075

M2 / 0.2N·m (max.0.25N·m)

M2.5 / 0.5N·m (max.0.6N·m)

-

For AE

………

, L1, L2, N/L3 are indicated instead R/L1, S/L2, T/L3 respectively.

Keys

Name

Description

Mode key

Increment
key

Decrement
key

RUN key

STOP/RESET
key

Enter key

Switches between the command setting and the data 
settings, and between the basic function mode and the 
expended function mode.

Ŷ

Status transition

Changes the set values, parameters and Commands.

Starts the operation. Forward/Reverse rotation 
depends on the ‘F004’ setting.

Stops the operation. Functions as the Reset key if an 
error occurs.

Enters and stores the data.

Hold down the Mode key for 3 seconds to jump  to 
‘d001'.

or

0.0 to 400.0

0.0 to 999.9

0.00 to 9999.
(Output frequency×conversion factor of b086)
0. to 600.

0. to 9999.
0. to 9999.
0.0 to 200.0

0. to 9999.

0.0 to 999.9

F: forward/ o: stop/ r: reverse

Parameter 

No.

Function name

Output frequency 
monitor

Monitor or data range

d001

Output current monitor

d002

Output frequency monitor
(after conversion)

d003

PID feedback value
monitor

d004

d007

Output voltage monitor

d013

Total RUN time

d016

Power ON time monitor
Fin temperature
monitor

d017
d018

Fault frequency
monitor

d080

Fault monitor1 (latest)

d081

Fault monitor2
Fault monitor3

d082
d083

DC voltage monitor

d102

0.0 to 100.0

Electric thermal monitor

d104

Starting frequency to max. frequency

Output frequency
setting / monitor

F001

0.01 to 3000.

Acceleration time1/
2nd acceleration time1

F002 / F202

0.01 to 3000.

Deceleration time1/
2nd deceleration time1

F003 / F203

00: forward/ 01: reverse

Operator rotation
direction selection

F004

00: Digital Operator (volume)/ 01: Terminal/
02: Digital Operator (F001)/
03: Modbus communication/
10: Frequency operation result

Frequency reference 
selection/
2nd frequency 
reference selection

A001 / A201

01: Terminal/ 02: Digital Operator/
03: Modbus communication

RUN command 
selection/ 2nd RUN 
command selection

A002 / A202

Base frequency/
2nd base frequency

A003 / A203

0.00 to 9999.
(Valid when the PID function is selected.)

30 to max. frequency [A004/A204]

Maximum frequency/
2nd maximum
frequency

A004 / A204

30. to 400.

FV/FI selection

A005

02: Switch between FV/ Volume via terminal AT
03: Switch between FI/ Volume via terminal AT
04: FV input only/ 05: FI input only

Multi-step speed 
reference0/ 2nd multi-
step speed reference0

A020 / A220

0.0/ Starting frequency to max. frequency

Multi-step speed 
reference1 to 15

A021 to A035

0.0/ Starting frequency to max. frequency

Jogging frequency

A038

0.00/ Strating frequency to 9.99

Jogging stop selection

A039

00: Free run on jogging stop
01: Deceleration stop on jogging stop
02: DC injection braking on jogging stop

Output voltage gain/
2nd output voltage gain

A045 / A245

20. to 100.

Acceleration pattern 
selection

A097

Deceleration pattern 
selection

A098

Retry selection

b001

Allowable momentary 
power interruption time

b002

00: Line/ 01: S-shape curve

00: Alarm/ 01: 0Hz start
02: Frequency matching start
03: Trip after frequency matching deceleration 

stop

0.3 to 25.0

Carrier frequency

b083

2.0 to 12.0

Initialization selection

b084

00: Clear the trip monitor
01: Initialize data
02: Clear and initialize

Overvoltage LAD stop 
function

b130

00: Disable/ 01: Enable

Overvoltage LAD stop 
function level

b131

200V class: 330 to 395
400V class: 660 to 790

Multi-function input1 
selection/ 
2nd multi-function 
input1 selection

C001 / C201

Multi-function input2 
selection/ 
2nd multi-function 
input2 selection

C002 / C202

Multi-function input3 
selection/ 
2nd multi-function 
input3 selection

C003 / C203

Multi-function input4 
selection/ 
2nd multi-function 
input4 selection

C004 / C204

Multi-function input5 
selection/ 
2nd multi-function 
input5 selection

C005 / C205

Multi-function input 1 ~
 5 operation selection

C011 to C015

Multi-function output 
terminal P1 selection

C021

Relay output (MA,MB) 
function selection

C026

AM selection

C028

00: FW(forward)/ 01: RV(reverse)/ 
02: CF1(multi-step speed setting binary1)/ 
03: CF2(multi-step speed setting binary2)/ 
04: CF3(multi-step speed setting binary3)/ 
05: CF4(multi-step speed setting binary4)/ 
06: JG(jogging)/ 07: DB(external DC injection 
braking)/ 08: SET(2nd control)/ 
09: 2CH(2-step acceleration/deceleration)/ 
11: FRS(free run stop)/ 12: EXT(external trip)/ 
13: USP(USP function)/ 15: SFT(soft lock)/ 
16: AT(analog input switch)/ 18: RS(reset)/ 
19: PTC(thermistor input)/ 20: STA(3-wire start)/ 
21: STP(3-wire stop)/ 22: F/R(3-wire forward/
reverse)/ 23: PID(PID enable/disable)/ 
24: PIDC(PID integral/reset)/ 27: UP(UP/DWN 
function accelerated)/ 28: DWN(UP/DWN f
unction decelerated)/ 29: UDC(UP/DWN function 
data clear)/ 31: OPE(forward operator)/ 
50: ADD(frequency addition)/ 51: F-TM(forced 
terminal block)/ 52: RDY(ready function)/ 
53: SP-SET(special 2nd function)/ 64: EMR
(emergency shut off)/ 255: No function

00: N.O.
01: N.C.

00: RUN(during RUN)/01:FA1(constant speed 
reached)/ 02: FA2(set frequency min. reached)/ 
03: OL(overload warning)/ 04: OD(PID 
excessive deviation)/ 05: AL(alarm output)/ 
06: Dc(disconnection defected)/ 07: FBV(PID 
FB value output)/ 08: NDc(Network error)/ 
09: LOG(logic operation output)/ 
10: ODc(communication option, disconnected)/ 
43: LOC(light load defection)
00: Output frequency/ 01: Output current

C031

00: NO contact at MA, NC contact at MB
01: NC contact at MA, NO contact at MB

Multi-function output 
Terminal P1 contact 
selection

C036

Relay output (MA,MB) 
contact selection

H003 / H203 Motor capacity selection/

2nd motor capacity 
selection

200V class: 0.2 to 7.5
400V class: 0.4 to 7.5

H004 / H204 Motor pole number 

selection/ 2nd motor 
pole number selection

2/ 4/ 6/ 8

3G3JX-A

…

SYSDRIVE Inverter

NT302XE

Cat.No.

Manual Name

INSTRUCTION MANUAL

Thank you for purchasing 3G3JX Inverter.
To ensure the safe operation, please be sure to read the safety 
precautions provided in this document along with all of the user 
manuals for the inverter. Please be sure you are using the most 
recent versions of the user manuals. Keep this instruction manual 
and all of the manuals in a safe location and be sure that they are 
readily available to the final user of the products.

OMRON Corporation

©OMRON Corporation 2013 All Rights Reserved.

3G3JX User’ s Manual

I558-E1

Ŷ

Standard Connection Diagram

Common

Common

Rotation direction
monitor

Error code (condition of occurrence) 

Æ

Output frequency 

Æ

 Output current 

Æ

Internal DC voltage 

Æ

 RUN time 

Æ

 ON time

Parameter 

No.

Function name

Monitor or data range

„

Indications and Meanings of Safety Information

Safety Precautions

In this user’s Manual, the following precautions and signal words 
are used to provide information to ensure the safe use of the 
3G3JX Inverter.
The information provided here is vital to safety. Strictly observe 
the precautions provided.

„

Meanings of Signal Words

WARNING

Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate 
injury or in property damage. 

CAUTION

Indicates an imminently hazardous situation which,
if not avoided, is likely to resuli in serious injury or 
death. Additionally there may be severe property 
damage.

„

Alert Symbols in this Document

Turn off the power supply and implement wiring correctly.
Not doing so may result in a serious injury due to an electric shock.

WARNING

Be sure to ground the unit. Not doing so may result in a serious injury 
due to an electric shock or fire.
(200V class:type-D grounding, 400V class:type-C grounding)

Do not remove the front cover during the power supply and 5 minutes 
after the power shutoff. Doing so may result in a serious injury due to 
an electric shock.
Do not operate the Operator or switches with wet hands.
Doing so may result in a serious injury due to an electric shock.

Inspection of the Inverter must be conducted after the power supply has 
been turned off. Not doing so may result in a serious injury due to an 
electric shock.
The main power supply is not necessarily shut off even if the emergency 
shut off function is activated.

Wiring work must be carried out only by qualified personnel. Not 
doing so may result in a serious injury due to an electric shock.

Do not change wiring, mode change switches(S7, S8), optional 
devices or  replace cooling fans while power is 
being supplied. Doing so may result in a serious injury due to an 
electric shock.