9
F3SJ-A-TS
Quick Installation Manual
5. Fix the unit on the wall.
Tightening with torque exceeding the recommended value too much may lead to a failure.
Wall-mounting screws are not included.
6. Align beams based on the indicators.
Please refer to instruction sheet about wiring examples.
■
Display Patterns of the Incident Light Level Indicator
Operation is possible with incident light level of 100% or more, but to ensure stability, operate when all incident light level
indicators.
Please do not tighten each screw one by one. Fully tighten all of them in a balanced manner at all places.
The angle adjustment range of mounting bracket F39-LJ3 is +/-10 degrees.
Wall-mounting screw (M5)
Wall-mounting screw (M5)
(Recommended tightening torque: 0.54N
•
m)
Backside mounting
Side mounting
Tighten securely
(Recommended tightening torque: 0.54N
•
m)
(Recommended tightening torque: 1.2N
•
m)
Tighten securely
Tighten securely
Align the unit to the
center of the angle
where five (5) light
intensity level
indicators turn ON
incident light level indicator
F
F
O
F
F
O
F
F
O
N
O
N
O
N
O
Safety Output
Incident light level
170% or
higher
Less than
170%
~
130%
Less than
130%
~
100%
Less than
100%
~
75%
Less than
75%
~
50%
Less than
50%
ON
OFF
Check
position
Step1
Mount
Step2
Align
beams
Step3
Mounting/Beam Alignment
Function Selection
Pre-Operation Checklist /
Maintenance Checklists
Summary of Contents for Sti F3SJ-A N Series
Page 14: ...F3SJ A P TS OMRON Corporation 2017 2020 All Rights Reserved Original instructions...
Page 16: ...2 F3SJ A TS 2 3 1 3 4 9...
Page 17: ...3 F3SJ A TS 4 F3SJ A TS...
Page 20: ...6 F3SJ A TS 5 2 1 2 2 3 2 3 5 1 E 0 1 P 0 0...
Page 21: ...7 F3SJ A TS 3 1 4 4 1 4 0 0 0 1 P...
Page 22: ...8 F3SJ A TS 5 6 100 5 1 F39 LJ3 10 0 0 1 P 1P 1 P...