background image

Safety 

Technology 

& Innovation 

Note:   The items listed under “Electrical connection” must be observed during commissioning. 

Commissioning 

Procedure 

1. Wiring  SR105E : 
Wire the SR105E  with the  OMRON STI  basic device  ac-

cording to your application (see Fig. 1 to Fig. 2). 
2. Wiring basic device: 
Wire  the  basic  device  according  to  the  required  Perform-

ance Level determined (see user information for the basic 

device). 
3. Wiring feedback loop: 
Wire the feedback loop as shown in Fig. 3 and Fig. 4. 
4. Wiring power supply:  
Connect the power supply to terminals A1 and A2 (Fig. 5). 
Warning:  Wiring only in de-energized state. 
5. Starting the device: 

 

Switch the operating voltage on. 

Warning: 
If the “Automatic start” starting behavior is set on the basic 

device, the safety contacts will close immediately. 
If the “Monitored manual start” starting behavior is set, close 

the  start  button  on  the  basic  device  to  close  the  safety 

contacts. 
The  LEDs  K1  and  K2  on  the  basic  device  and  on  the 

SR105E are lit. 
6. Triggering safety function: 
Open  the  emergency  stop  circuit  by  actuating  the  con-

nected  safety  switch.  The  safety  contacts  of  the  basic  de-

vice and the SR105E open immediately. 
7. Reactivation: 
Close  the  emergency  stop  circuit.  If  “Automatic  start”  is 

selected on the basic device, the safety contacts will close 

immediately. 
If the “Monitored manual start” starting behavior is set, close 

the  start  button  on  the  basic  device  to  close  the  safety 

contacts of the basic device and the SR105E. 

Depending on the application, the device must be wired with a ORMON STI basic device as shown in Fig. 1 to Fig. 2. If the 

devices are wired inside a control cabinet (minimum degree of protection IP54), the fault involving a short circuit between the 

activation lines can be ruled out (protected wiring space). Category 4, PL e according to EN ISO 13849-1 is thereby possible. 
If this fault cannot be ruled out, category 3, PL e is achieved. 

Applications 

Fig. 3: Feedback loop  

Contactors connected to the SR105E 

or the basic devices are monitored via 

the feedback loop of the basic device. 

K

A

 and K

B

 are the positively driven 

contacts of the connected contactor or 

expansion module. 

Fig. 2: Connection of several SR105E units to basic 

device 

If further SR105E units are to be integrated into the system, 

terminals S11 must be connected in parallel on all SR105E units. 

This also applies to terminals S10 and terminals S15/S16. 

Fig. 1: Connection of SR105E to basic device 

Wiring of the SR105E via only 4 lines: 
A safety contact of the basic devices (e.g. 13-14) activates the 

relays of the SR105E (S11 and S15/S16). 
Two lines on S23 and S24 are required for feedback/fault moni-

toring. A fault in the SR105E thereby prevents the entire safety 

chain from restarting. 
Earth faults in the control lines are detected in addition to inter-

nal faults. 

Wiring 

Feedback Loop 

SR105E 

User Information for SR105E  

Notice: 
In order to activate earth fault monitoring, S10 must  be  con-

nected to PE  (protective  earth)  on the AC115/230V devices. 

With AC/DC 24 V, connect PE only to the power supply unit 

according to EN60204-1. 

Fig. 4: Feedback Loop with Auto-Start 

Contactors connected to the SR105E or the 

basic devices are monitored via the feedback 

loop of the basic device. K

A

 and K

B

 are the 

positively driven contacts of the connected 

contactor or expansion module. 

Power supply  
and  
Safety contacts 

Fig. 5: 

Power supply A1 and A2. 
 
(Power supply according to techn. 

Data ) 

Fig. 6: 

Connecting load to safety contacts. 
 
(Figure shows example.  
Voltage „+V“ according to techn. 

Data) 

S12 

Summary of Contents for SR105E

Page 1: ... of the SR105E open immediately If a fault occurs in the SR105E this is detected by the basic device via terminals S23 and S24 Independent operation without basic device is not possible Electrical Connection When the 24 V version is used a control transformer according to EN 61558 2 6 or a power supply unit with electrical isolation from the mains must be connected External fusing of the safety co...

Page 2: ...ction IP54 the fault involving a short circuit between the activation lines can be ruled out protected wiring space Category 4 PL e according to EN ISO 13849 1 is thereby possible If this fault cannot be ruled out category 3 PL e is achieved Applications Fig 3 Feedback loop Contactors connected to the SR105E or the basic devices are monitored via the feedback loop of the basic device KA and KB are...

Page 3: ... C 0 6 o t C 5 1 V 4 2 C D e g n a r e r u t a r e p m e T C 0 4 o t C 5 1 V 5 1 1 0 3 2 C A 1 0 1 1 0 E D V N I D 2 n o i t a n i m a t n o c f o e e r g e D 1 0 1 1 0 E D V N I D 3 y r o g e t a c e g a t l o v r e v O g 0 3 2 x o r p p a t h g i e W 5 3 H T 5 1 7 0 6 N E o t g n i d r o c c a l i a r N I D g n i t n u o M Note Additional data can be requested from the manufacturer for applicati...

Page 4: ... applied OMRON Scientific Technologies Inc 6550 Dumbarton Circle Fremont CA 94555 U S A Directives applied EMC directive 2004 108 EC Machinery directive 2006 42 EC Standards applied EN ISO 13849 1 2008 AC 2009 EN 62061 2005 Fremont May 2014 Marty Krikorian Director Quality Control The signed EC Declaration of Conformity is included with the product RoHS directive 2002 95 EC Authorized Signer of De...

Page 5: ...stems Machine Automation Controllers MAC Programmable Controllers PLC Operator interfaces HMI Distributed I O Software Drives Motion Controls Servo AC Drives Motion Controllers Encoders Temperature Process Controllers Single and Multi loop Controllers Sensors Vision Proximity Sensors Photoelectric Sensors Fiber Optic Sensors Amplified Photomicrosensors Measurement Sensors Ultrasonic Sensors Vision...

Reviews: