16
Switch Mode Power Supply
S8VM
■
Remote Control Function
This function turns outputs ON and OFF using an external signal
while input voltage is applied, using the +RC pin (pin 7 on CN) and
the -RC pin (pin 8 on CN). Connect a switch or transistor to the +RC
and -RC pins to use the remote control function. When not using this
function, the +RC and -RC pins are shorted by using the standard
supplied connector.
Maximum input voltage: 12 V max.
Maximum allowable reverse voltage:
−
1 V max.
Sink Current: 3.5 mA
Note: 1. Use 2-conductor shielded cable or twisted-pair cable as
connection wire.
2. The remote control circuit is isolated from the input and out-
put circuits of the power supply.
3. Remove the standard supplied connector and prepare a
connector separately.
■
Power Failure Alarm Function
The power failure alarm indicator will light red to indicate an output
voltage error if overload, overvoltage, or overheat protection is acti-
vated, if a drop in the input voltage causes the output voltage to drop,
if the built-in fan motor stops, and during remote control standby. The
alarm is also output externally by a transistor.
Transistor output: 30 VDC max., 50 mA max.
Residual voltage when ON: 2 V max.
Leakage current when OFF: 0.1 mA max.
Alarm detection voltage: Approx. 80% of output voltage setting
During detection, the transistor is OFF (with no continuity across pins
11 and 12 on CN), and the LED (red) lights.
Note: 1. This function monitors the voltage at the Power Supply out-
put terminals. To check actual voltage, measure the voltage
on the load side.
2. Outputs are forced OFF if the built-in fan motor stops
(S8VM-15224C only).
3. Remove the standard supplied connector and prepare a
connector separately.
■
Inrush Current, Start Up Time,
Output Hold Time
■
Input Current Waveform When
Input Is Turned ON
(The following examples show typical waveforms.)
S8VM-300
@@
C
100 VAC, Load ratio: 100%
200 VAC, Load ratio: 100%
+
RC Level for
−
RC
Output
Built-in Fan Motor
Short or L (0 to 0.8 V) ON
Rotate
Open or H (2.4 to 12 V) OFF
Stop
TR
SW
+
RC
−
RC
S8VM
CN
PF-C
PF-E
S8VM
CN
Vce max.: 30 VDC
Ic max.: 50 mA
Start up time
Hold time
Inrush current on input application
90%
95%
Input ON
Input OFF
AC input
voltage
AC input
current
Output
voltage
100 ms
AC input
current
(10 A/DIV)
AC input
voltage
Output
voltage
100 ms
AC input
current
(10 A/DIV)
AC input
voltage
Output
voltage