background image

S8VK-X

23

• Adjust the output voltage difference of each Power Supply to 

50 mV or less, using the output voltage adjuster (V. ADJ).

• There is no current balancing function for S8VK-X. A high output 

voltage unit may work at overcurrent state and in this situation, a 
life of a Power Supply will be extremely short. After adjusting the 
output voltage, confirm the output current of the Power Supplies 
balances.

• During parallel operation, UL1310 Class 2 output and UL 60950-1, 

UL 62368-1, EN 60950-1, and EN62368-1 LPS output are 
excluded.

• For Parallel Operation, to balance the current of the each unit, the 

length and thickness of each wire connected to the load and each 
unit must be same as much as possible.

• If you use the output voltage may drop by several volts if the load 

changes rapidly (e.g., if the load starts or is disconnected).  Use the 
S8VK-R or connect external diodes as shown in the figure.
For parallel operation with 30 W, 60 W, 90 W or 120 W Power 
Supplies, use the S8VK-R10. For parallel operation with 240 W 
Power Supplies, use the S8VK-R20.

• Do not use parallel operation when there is the possibility that the 

input voltage will vary outside of the rated input range.

• Use the following information as a guide to the diode type, dialectic 

strength, and current.

<Backup Operation>

Backup operation is possible if you use two Power Supplies of the 
same model.
Even if one Power Supply fails, operation can be continued with the 
other Power Supply.
Make sure that the maximum load does not exceed the capacity of 
one Power Supply.
Use the S8VK-R or connect external diodes.
For backup operation with 30 W, 60 W, 90 W or 120 W Power 
Supplies, use the S8VK-R10. For backup operation with 240 W 
Power Supplies, use the S8VK-R20.

• Use the following information as a guide to the diode type, dialectic 

strength, and current.

Two phases application for Single phase models

For All Single phase Models, S8VK-X

Basically OMRON single phase power supply can be used on two-
phases of a 3–phase-system when some of conditions satisfy like 
below.

1.

The supplying voltage is below the maximum rated input.
OMRON Power supply allows the input voltage equivalent or less 
than 240 VAC+10%. 
Please confirm the input voltage between two lines if the input 
voltage satisfies this condition before connecting.

2.

The external protector is needed on N input line to secure a safety. 
N line has no protection of a fuse internally. 
An appropriate fuse or circuit breaker should be connected on N 
input line like the following.

Type

Schottky Barrier diode

Dielectric strength (V

RRM

)

Twice the output voltage or above

Forward current (I

F

)

Twice the rated output current or 

above

INPUT

S8VK-X

S8VK-R

S8VK-X

+V

-V

+V

-V

INPUT

IN 1

IN 2

+V

-V

Load

+V

-V

+V

-V

INPUT

INPUT

S8VK-X

S8VK-X

Load

Type

Schottky Barrier diode

Dielectric strength (V

RRM

)

Twice the output voltage or above

Forward current (I

F

)

Twice the rated output current or 

above

INPUT

S8VK-X

S8VK-R

S8VK-X

+V

-V

+V

-V

INPUT

IN 1

IN 2

+V

-V

Load

+V

-V

+V

-V

INPUT

INPUT

S8VK-X

S8VK-X

Load

An external 
f

u

se or a  

circ

u

it 

b

reaker

max. 240 

V

AC+10

%

Internal 
F

u

se

Power Supply

N

L

L

1

L

2

L

3

PE

Summary of Contents for S8VK-X

Page 1: ...t function at 150 240 and 480 W Side by side mounting possible up to 55 C UL Class 2 conformance 90 W or less Complies with EN IEC 61558 2 16 Coated PCBs for better resistance to environment Model Num...

Page 2: ...ed output voltage DC Rated output current Maximum boost current Model number 30 W 100 to 240 VAC allowable range 85 to 264 VAC 90 to 350 VDC 5 V 5 A 1 6 A S8VK X03005 EIP 60 W 12 V 4 5 A 2 5 4 A S8VK...

Page 3: ...ervoltage Protection on page 8 for details Series operation Yes For up to two Power Supplies external diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on...

Page 4: ...to two Power Supplies external diodes are required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicato...

Page 5: ...al diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicator Yes LED Red Indication monitor...

Page 6: ...e satisfied Voltage range Do not use an inverter output for the product Inverters with an output frequency of 50 60 Hz are available but the rise in the internal temperature of the product may result...

Page 7: ...rement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1 digit Peak hold current measurement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1...

Page 8: ...s been removed Communication Specifications Note 1 Internal parts may possibly deteriorate or be damaged if a short circuited or overcurrent state continues during operation 2 Internal parts may possi...

Page 9: ...pply 3 If you do not change the communication settings during step 4 settings will return to their prior values once the communication reset is ended Switching Indications All indicators of the indica...

Page 10: ...approximately 15 years after purchase even if the replacement time calculation for years and percentage do not appear 2 The replacement time is accelerated or decelerated according to operating condi...

Page 11: ...e product s time powered on is measured as continuous run time and the continuous run time increases in 1 min steps with use Continuous run time will be reset when power is turned off Time Chart Note...

Page 12: ...Inrush current protection circuit Smoothing circuit Rectifier smoothing circuit Overvoltage detection circuit Current detection circuit Overcurrent circuit 250 VAC 8 0 A HBC Photocoupler V2 V1 V1 V2...

Page 13: ...e detection circuit Voltage detection circuit Photocoupler Overcurrent detection circuit S8VK X24024 EIP Harmonic current emissions Fuse N1 N2 HBC Smoothing circuit 8 0 A Rectifier smoothing circuit L...

Page 14: ...W 240 W 480 W S8VK X09024A EIP S8VK X12024A EIP S8VK X24024A EIP S8VK X48024A EIP Without Indication Monitor 30 W 60 W 90 W 120 W 240 W 480 W S8VK X03005 EIP S8VK X06012 EIP S8VK X06024 EIP S8VK X090...

Page 15: ...ut voltage adjuster V ADJ Use to adjust the output voltage 14 Main display white Displays measured values 15 Operation indicator white V Lights up when the output voltage is indicated A Lights up duri...

Page 16: ...ont side by side mounting This Power Supply can be used at an altitude of 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve Horizontal separation 15 mm or mor...

Page 17: ...10 4 7 2 3 90 1 86 40 1 S8VK X03005 EIP 30 W S8VK X06012 EIP 60 W S8VK X06024 EIP 60 W The above diagram shows S8VK X06024 EIP 2 3 3 5 5 4 5 4 Sliding 10 max Rail stopper 78 55 90 1 15 4 7 90 1 86 55...

Page 18: ...1 4 1 111 4 5 4 38 1 5 4 4 Rail stopper S8VK X24024 EIP 240 W The above diagram shows S8VK X24024A EIP 10 0 6 0 6 19 8 108 8 124 1 22 Sliding 8 max 5 2 2 3 117 121 4 1 111 4 5 4 60 1 0 9 7 5 4 Rail st...

Page 19: ...dels S82Y VK10F 41 35 0 1 40 50 35 25 10 7 3 2 4 5 dia 0 1 t 1 0 35 64 t 2 0 80 60 0 1 55 0 1 13 3 4 5 dia 0 1 Left side mounting Right side mounting 25 0 1 140 0 1 150 38 5 4 t 2 0 4 4 5 dia 0 1 240...

Page 20: ...nd surge Mounting Take adequate measures to ensure proper heat dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when m...

Page 21: ...ires in order to prevent smoking or ignition Recommended Wire Type Input crossover wiring can be used for the input side of this Power Supply Do not use crossover wiring for more than five Power Suppl...

Page 22: ...by using two Power Supplies You can make positive negative outputs with any of the models If positive and negative outputs are used connect Power Supplies of the same model as in the following figure...

Page 23: ...ply Make sure that the maximum load does not exceed the capacity of one Power Supply Use the S8VK R or connect external diodes For backup operation with 30 W 60 W 90 W or 120 W Power Supplies use the...

Page 24: ...release hole 2 With the flat blade screwdriver still inserted into the release hole insert the wire into the terminal hole until it strikes the terminal block 3 Remove the flat blade screwdriver from...

Page 25: ...n it with excessive force Do not place heavy objects on the cord This may cause a wire to be broken Separate the communication cable into a high voltage and high current power line to prevent inductio...

Page 26: ...voltage such as a lightning inrush is applied to the input In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether t...

Page 27: ...wer Supply Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performa...

Page 28: ...ears Warranty 1 1 Refer to Period and Terms of Warranty on page 36 for details Model Number Structure Model Number Legend Note Not all combinations are possible Refer to List of Model number in Orderi...

Page 29: ...85 C with no condensation or icing Ambient operating humidity 95 Storage humidity 95 max Vibration resistance 10 to 55 Hz maximum 5 G 0 42 mm half amplitude for 2 h each in X Y and Z directions Shock...

Page 30: ...erating curve by 0 8 to reduce the load Does not apply for face up mounting 0 20 40 60 80 100 120 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Load ratio Operating temperature C Note If using at an altitu...

Page 31: ...Name Model number Dimensions Appearance Front mounting bracket S82Y VS10F Side mounting bracket S82Y VS10S 1 2 90 1 86 3 5 5 4 Rail Stopper 78 55 4 7 Sliding 10 max 90 1 5 4 32 1 S8V NFS203 S8V NFS20...

Page 32: ...lt from aluminum abrasion Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Rail Mat...

Page 33: ...oduct in locations subject to direct sunlight Do not use locations where liquids foreign matter or corrosive gases may enter the interior of the product Mounting Take adequate measures to ensure prope...

Page 34: ...wires for one product When using crossover wiring select wiring materials suitable for the total current that will flow to terminals Stripping length DIN Rail Mounting To mount the Block on a DIN Rai...

Page 35: ...he following figure Recommended Flat blade Screwdriver Use a flat blade screwdriver to connect and remove wires Use the following flat blade screwdriver The following table shows manufacturers and mod...

Page 36: ...e following types of failures 1 Failures that result from handling or operation of the product under conditions or in environments that are not given in this document and not given in any other specif...

Page 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 38: ...oofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 11...

Reviews: