S8VK-X
11
Difference between Expected Life and Replacement Time
OMRON calculates the expected life based on the following
conditions.
1.Rated input voltage
2. Load rate: 50%
3. Ambient temperature: +40
°C
4. Standard mounting
Note:
As the values were calculated using an aluminum electrolytic
condenser temperature rise test, they are not guaranteed. Use
this data as a reference for maintenance and replacement time
calculation.
The expected life span of the S8VK-X is 10 years minimum.
Also, a replacement time calculation function is included among the
functions of the S8VK-X. The replacement time is the service life (the
Power Supply's internal temperature is monitored at all times) of the
internal electrolytic capacitor in actual operating conditions, and
varies according to the customers operating conditions. 15 years is
taken as the maximum period of the maintenance forecast.
Total Run Time
The accumulated value of the product's time powered on is measured
as the total run time.
(With indication monitor)
Total run time increases in (kh) steps with use.
(Communication)
Total run time increases in (h) steps with use.
Time Chart
Note: 1.
The total run time does not include the time that the Power
Supply is OFF.
2.
The total run time measures the total time that power is
being supplied and is not related in any way to deterioration
in the electrolytic capacitor built into the Power Supply or to
the effects of the ambient temperature.
Continuous Run Time (Communication Only)
The product's time powered on is measured as continuous run time,
and the continuous run time increases in 1 (min) steps with use.
Continuous run time will be reset when power is turned off.
Time Chart
Note: 1.
The continuous run time does not include the time that the
Power Supply is OFF.
2.
The continuous run time measures the total time that power
is being supplied and is not related in any way to
deterioration in the electrolytic capacitor built into the Power
Supply or to the effects of the ambient temperature.
Self-Diagnostics Function
Note: 1.
External noise is probable as a cause of
and
errors.
2.
When
is displayed, indication switching is not possible.
3.
Operation out of the derating curve area, ventilation errors, and incorrect mounting direction are probable as a cause of
and
errors.
4.
Pressing the indication switching key on the
and
display screen will return to the normal display screen.
5.
When
is displayed, the years/percentage until replacement will become
and
% respectively.
Total run time
0 kh
AC input
Continuous run time
0 min
AC input
Main display
Alarm indicator
Status name
Details
Restoration method
Lit
Measurement
abnormality
Output voltage, output current,
etc., cannot be measured
normally due to noise
Automatic reset.
Lit
Overheating alarm
Overheated status has continued
for 1 to 180 minutes
Automatic reset.
Lit
Product overheat
abnormality
Overheated status has continued
for more than 180 minutes
Replace the Power Supply, as internal parts may be
deteriorated.
Lit
Memory error
If there is an internal memory
error, damage to data, etc., may
occur
Turn the AC input OFF then ON again.
If the Product is not reset, contact the dealer.
(Flashing)
(Flashing)