Omron S8VK-W Series Manual Download Page 25

S8VK-WA/S8VK-WB

25

S8VK-W

A

S8VK-WB

Common Accessories

Common Precautions

Recommended circuit breakers and fuses

• Product failure may result in fire or electric shocks. Therefore, 

always use the recommended circuit breaker or fuse.

• To ensure conformance to safety standards, and secure safety of 

the Unit, connect an input to the Unit via the recommended circuit 
breakers or fuses indicated in the table below.

• A circuit breaker or fuse can be changed only by the indicated 

person or skilled person.

Note:

For the S8VK-WB, the DC input is not compliant with Safety 

standards.

• If multiple Units are used through crossover wiring, select the 

circuit breaker or fuse in view of the input current and inrush 
current.

Wiring method

• Connect the input as shown in the figure below.
• In the case of a three-phase four-wire system, do not connect the 

ground and neutral wire, but connect the other three wires to “L1/
+, L2, L3/-”.

Wiring

• This is the protective earth terminal specified in the safety 

standards. Connect the ground completely. Electric shock or 
malfunction may occur if the ground is not connected completely.

• Minor fire may possibly occur. Ensure that DC input and output 

terminals are wired correctly.

• When you insert wires or insert a screwdriver into a release hole, 

do not press down on the terminal block with a force of 40 N or 
greater (100 N or greater for the output terminal block of S8VK-
W

@

960

@@

 only).

• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a 

release hole on the terminal block. The terminal block may be 
damaged.

• Insert a flat-blade screwdriver into the release holes at an angle. 

The terminal block may be damaged if you insert the screwdriver 
straight in.

• Do not allow the flat-blade screwdriver to fall out while it is inserted 

into a release hole.

• Do not bend a wire past its natural bending radius or pull on it with 

excessive force. This may cause a wire to be broken.

• Do not insert more than one wire into each terminal insertion hole.
• Do not pre-solder the ends of the wires. Doing so will inhibit proper 

connection.

• Be sure to remove the sheet covering the S8M for machining 

before power-ON so that it does not interfere with heat dissipation.

• If there is a possibility of vibration or shock, please use wires and 

stranded wires with ferrules.

• Minor fire may occasionally occur.

Always check the voltage of the equipment when replacing the 
Unit, and be sure to use a conforming product.

• Use the following material for the wires after confirming the rating 

of the wires in order to prevent smoking or ignition.

• Use copper stranded or solid wires. However, solid wires can not 

be used for the S8VK-W

@

960

@@

 output terminal.

Model

Input

Recommended product

(per single Unit)

S8VK-WA24024

Three-phase

Circuit breaker:

240 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

Single-phase

Two-phase

Circuit breaker:

240 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

350 VDC min., 6 A

S8VK-WA48024

Three-phase

Circuit breaker:

240 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

Single-phase

Two-phase

Circuit breaker:

240 VAC min., 7 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

350 VDC min., 8 A

S8VK-WA96024

Three-phase

Circuit breaker:

240 VAC min., 8 to 20 A, 

Type B, C, or D characteristics

Single-phase

Two-phase

Circuit breaker:

240 VAC min., 13 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

350 VDC min., 15 A

S8VK-WB24024

S8VK-WB24048

Three-phase

Circuit breaker:

480 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

Two-phase

Circuit breaker:

480 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

600 VDC min., 5 A

S8VK-WB48024

S8VK-WB48048

Three-phase

Circuit breaker:

480 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

Two-phase

Circuit breaker:

480 VAC min., 4 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

600 VDC min., 5 A

S8VK-WB96024

S8VK-WB96048

Three-phase

Circuit breaker:

480 VAC min., 6 to 20 A, 

Type B, C, or D characteristics

Two-phase

Circuit breaker:

480 VAC min., 8 to 20 A, 

Type B, C, or D characteristics

DC

Fuse:

Fast-acting type, 

600 VDC min., 8 A

L1
L2
L3
N

PE

TN-S

TN-C

PEN

L3

L2

L1

PE

L3

(L2)

L1

Single-phase

Input wiring (TN-S, TN-C, single-phase)

Circuit 
breaker

Circuit 
breaker

Circuit 
breaker

Input wiring (TT, IT, DC)

L1
L2
L3

N

TT

DC

IT

L3

L2

L1

Circuit 
breaker

Circuit 
breaker

Fuse

Single-phase

Circuit 
breaker

PE

N

L

PE

-

+

Summary of Contents for S8VK-W Series

Page 1: ... 40 to 70 C 1 Side by side Mounting enabled 1 2 Complies with SEMI F47 0706 standard 3 Certification for 3 000 m altitude 3 Coated PCBs for Better Resistance to Environment Equipped with signal output that indicates DC OK and the overload status Five years Warranty 1 For details refer to Derating Curves on page 9 and 20 2 Refer to the Front Side by side mounting on page 24 3 For details refer to S...

Page 2: ... Model Number Legend Not all combinations are possible Refer to List of Models in Ordering Information below 1 Rated input voltage 2 Power rating 3 Output voltage Ordering Information List of Models Accessories Order separately Refer to page 22 for S8VK WA S8VK WB Common Accessories Output voltage Power rating 240 W 480 W 960 W 24 V Released Released Released Refer to Safety Precautions on page 24...

Page 3: ...s typ Additional functions Overload protection Yes automatic reset intermittent operation type Refer to Overload Protection on page 5 Overvoltage protection Yes 130 or higher of rated output voltage power shut off shut off the input voltage and turn on the input again Refer to Overvoltage Protection on page 5 Series operation Yes For up to two Power Supplies external diodes required Parallel opera...

Page 4: ...iance To comply with PELV output requirements for EN IEC 60204 1 ground the negative side of the output V to a protective earth PE EN IEC 61558 2 16 The S8VK WA was designed based on EN IEC 61558 2 16 Currently IEC 61558 2 17 has been replaced by IEC 61558 2 16 When certification was received for EN IEC 60204 1 Machinery Safety it was necessary to go through a control transformer to the control ci...

Page 5: ... output voltage is more than 90 of the rated output voltage and the internal MOS FET relay is conducted turned ON Note 1 The output voltage may be generated even if the indicator does not light Be sure to check the output voltage when connecting to the load 2 This function monitors the voltage at the power output terminals To check the voltage accurately measure the voltage at the load end 3 If th...

Page 6: ...cuiting change to a product with less load or larger output capacity z z The product may have failed or the overvoltage protection may have been activated for the product To check for overvoltage protection turn the input power OFF and then turn it ON again after 3 minutes or more has elapsed If no output voltage is output the product may have failed Replace the product No input voltage is being s...

Page 7: ...tection circuit Smoothing circuit Harmonic current suppression circuit DC OK COM DC OUTPUT L1 1 INPUT L1 2 L2 1 L2 2 L3 2 L3 1 out I 100 S8VK WA48024 480 W S8VK WA96024 960 W Overcurrent detection circuit Current detection circuit Smoothing circuit Harmonic current suppression circuit Rectifier Noise Filter Photocoupler Inrush current protection circuit Drive control circuit Overcurrent circuit V1...

Page 8: ...se terminals 9 V2 10 V1 11 V2 12 V3 13 INPUT OK Indicator INPUT OK Green Lights up when the input voltage exceeds the lower limit value of the permissible range 14 Iout 100 Indicator Iout 100 Yellow The Iout 100 Indicator lights up when the output current exceeds the rated output current 15 DC OK Indicator DC OK Green Lights up when the output voltage is more than 90 of the rated output voltage 16...

Page 9: ...shaded area time is required to reach the rated output voltage after the input voltage is applied A Standard mounting B Face up mounting C Front side by side mounting This Power Supply can be used at an altitude of up to 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve 240 W 480 W 960 W Horizontal separation 15 mm or more 240 W 480 W 960 W Horizontal sepa...

Page 10: ... 54 4 53 8 5 4 6 5 0 55 19 8 1 2 0 6 121 4 1 55 1 0 6 124 1 10 S8VK WA24024 5 2 8 0 max when sliding 121 4 1 0 6 0 6 1 1 1 10 20 8 7 5 0 9 5 17 3 52 7 53 8 117 111 4 124 1 5 4 6 5 0 55 19 8 65 1 S8VK WA48024 5 17 3 51 1 53 8 121 4 1 117 111 4 0 6 0 6 124 1 1 1 1 10 5 4 6 5 0 55 19 8 118 1 47 2 10 0 9 5 2 8 0 max when sliding S8VK WA96024 ...

Page 11: ... operate at an ambient temperature of 40 to 70 C 1 Side by side Mounting enabled 1 2 Complies with SEMI F47 0706 standard 3 Certification for 3 000 m altitude 3 Coated PCBs for Better Resistance to Environment Equipped with signal output that indicates DC OK and the overload status 1 For details refer to Derating Curves on page 20 2 Refer to the Front Side by side mounting on page 24 3 For details...

Page 12: ...960 W 24 V Released Released Released 48 V Released Released Released S8VK WB Series name 2 3 1 Code Rated input voltage B 380 to 480 Code Power rating 240 240 W 480 480 W 960 960 W Code Output voltage VDC 24 24 V 48 48 V Power rating Rated input voltage Rated output voltage VDC Rated output current Maximum boost current Model 240 W Three phase two phase 380 to 480 VAC Allowable range Three phase ...

Page 13: ...f shut off the input voltage and turn on the input again Refer to Overvoltage Protection on page 16 Series operation Yes For up to two Power Supplies external diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 28 INPUT OK Indicator Yes LED Green DC OK Indicator Yes LED Green Iout 100 Indicator Yes LED Yellow DC OK Signal Output Yes MOS FET relay...

Page 14: ...d turn on the input again Refer to Overvoltage Protection on page 16 Series operation Yes For up to two Power Supplies external diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 28 INPUT OK Indicator Yes LED Green DC OK Indicator Yes LED Green Iout 100 Indicator Yes LED Yellow DC OK Signal Output Yes MOS FET relay output 30 VDC max 50 mA max Io...

Page 15: ...r the input voltage is input 11 MTBF is calculated according to JEITA RCR 9102 12 Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 32 for details 13 When using 2 phase input conforms to EN 61000 3 2 under the following condition 960W At the rated output voltage and 80 or less than the rated output current 14 Refer to Standard Compliance below for...

Page 16: ... output voltage is more than 90 of the rated output voltage and the internal MOS FET relay is conducted turned ON Note 1 The output voltage may be generated even if the indicator does not light Be sure to check the output voltage when connecting to the load 2 This function monitors the voltage at the power output terminals To check the voltage accurately measure the voltage at the load end 3 If th...

Page 17: ...cuiting change to a product with less load or larger output capacity z z The product may have failed or the overvoltage protection may have been activated for the product To check for overvoltage protection turn the input power OFF and then turn it ON again after 3 minutes or more has elapsed If no output voltage is output the product may have failed Replace the product No input voltage is being s...

Page 18: ...suppression circuit Smoothing circuit Rectifier smoothing circuit Signal Output Signal Output Current detection circuit Overcurrent detection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler Drive control circuit Overcurrent circuit V1 V2 V1 V3 V2 DC OUTPUT COM DC OK L1 1 L1 2 L2 1 L2 2 L3 1 L3 2 INPUT I 100 out ...

Page 19: ...erminals 9 V2 10 V1 11 V2 12 V3 13 INPUT OK Indicator INPUT OK Green Lights up when the input voltage exceeds the lower limit value of the permissible range 14 Iout 100 Indicator Iout 100 Yellow The Iout 100 Indicator lights up when the output current exceeds the rated output current 15 DC OK Indicator DC OK Green Lights up when the output voltage is more than 90 of the rated output voltage 16 Out...

Page 20: ...ote 1 Apply the rated input voltage for both three phase and two phase 2 In the shaded area time is required to reach the rated output voltage after the input voltage is applied A Standard mounting B Face up mounting C Front side by side mounting This Power Supply can be used at an altitude of up to 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve 240 W 4...

Page 21: ...5 8 54 4 53 8 5 4 6 5 0 55 19 8 1 2 0 6 121 4 1 55 1 0 6 124 1 10 S8VK WB240 5 2 8 0 max when sliding 121 4 1 0 6 0 6 1 1 1 10 20 8 7 5 0 9 5 17 3 52 7 53 8 117 111 4 124 1 5 4 6 5 0 55 19 8 65 1 S8VK WB480 5 17 3 51 1 53 8 121 4 1 117 111 4 0 6 0 6 124 1 1 1 1 10 5 4 6 5 0 55 19 8 118 1 47 2 10 0 9 5 2 8 0 max when sliding S8VK WB960 ...

Page 22: ...eparately DIN Rail Mounting Parts Order Separately Accessories Order separately Product name Model Front Mounting Bracket for 240 W S82Y VKW20F Front Mounting Bracket for 480 W S82Y VKW40F Front Mounting Bracket for 960 W S82Y VKW90F Part name Model Support Rail Aluminum PFP 100N PFP 50N PFP 100N2 End Plate PFP M ...

Page 23: ...nit Name Model Dimensions Appearance Front mounting bracket For 240 W models S82Y VKW20F Front mounting bracket For 480 W models S82Y VKW40F Front mounting bracket For 960 W models S82Y VKW90F Two 4 5 dia 0 1 35 0 1 40 R1 5 35 7 3 1 40 25 t 1 2 55 Two 4 5 dia 0 1 35 0 1 35 40 40 25 7 3 t 1 2 R1 5 1 65 118 106 85 0 1 1 R1 5 Three 4 5 dia 0 1 35 40 7 3 25 t 1 2 Mounting Rail Material Aluminum PFP 10...

Page 24: ...gnition or burning If the input is connected to a UPS do not connect a UPS with a square wave output Doing so will cause the internal temperature of the product to increase possibly causing smoking or burning Mounting Take adequate measures to ensure proper heat dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when m...

Page 25: ...ion Be sure to remove the sheet covering the S8M for machining before power ON so that it does not interfere with heat dissipation If there is a possibility of vibration or shock please use wires and stranded wires with ferrules Minor fire may occasionally occur Always check the voltage of the equipment when replacing the Unit and be sure to use a conforming product Use the following material for ...

Page 26: ...d protection function When this happens the Iout 100 indicator will blink in accordance with the intermittent operation and the Iout 100 signal output will repeatedly turn ON and OFF The shortest ON time of the Iout 100 signal output during intermittent operation is 5 ms Specifications of the Signal Output Terminals between DC OK Signal Output Terminal and COM Terminal and between Iout 100 Signal ...

Page 27: ...g ratings 2 Though Power Supplies having different specifications can be connected in series the current flowing through the load must not exceed the smaller rated output current Be sure to check that the Iout 100 indicator is not lit or the Iout 100 signal output is turned OFF before using Making Positive Negative Outputs The outputs are floating outputs i e the primary circuits and secondary cir...

Page 28: ...D1 and D2 Also the diodes will cause a power loss equivalent to the Power Supply output current IOUT times the diode forward voltage VF Therefore cooling measures must be implemented so that the temperature of the diodes decreases to the catalog value or lower Because of the load power and power loss due to the diodes do not exceed the rated power of one Power Supply rated output voltage rated out...

Page 29: ...rewdriver still inserted into the release hole insert the wire into the terminal hole until it strikes the terminal block 3 Remove the flat blade screwdriver from the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block The insulation distance is still satisfied although some of ...

Page 30: ... mm2 AWG Phoenix Contact Weid muller Wago 0 25 24 8 10 AI 0 25 8 H0 25 12 FE 0 25 8N YE 10 12 AI 0 25 10 0 34 22 8 10 AI 0 34 8 H0 34 12 FE 0 34 8N TQ 10 12 AI 0 34 10 0 50 20 8 10 AI 0 5 8 H0 5 14 FE 0 5 8N WH 10 12 AI 0 5 10 H0 5 16 FE 0 5 10N WH 0 75 18 8 10 AI 0 75 8 H0 75 14 FE 0 75 8N GY 10 12 AI 0 75 10 H0 75 16 FE 0 75 10N GY 1 1 25 18 17 8 10 AI 1 8 H1 0 14 FE 1 0 8N RD 10 12 AI 1 10 H1 0...

Page 31: ...d The internal protection may operate if a large amount of surge voltage such as a lightning inrush is applied to the input In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether the load is in overload status or is short circuited Remove the load wires when checking Can be checked depending on whether or not the I...

Page 32: ...Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the service life is reduced by half for each 10 C rise in temperature Arrhenius law When the capacity reduction life of the electrolytic capacitor is reached the Power Supply fail...

Page 33: ...UARTERS Chicago IL USA 847 843 7900 800 556 6766 automation omron com Controllers I O Machine Automation Controllers MAC Motion Controllers Programmable Logic Controllers PLC Temperature Controllers Remote I O Robotics Industrial Robots Mobile Robots Operator Interfaces Human Machine Interface HMI Motion Drives Machine Automation Controllers MAC Motion Controllers Servo Systems Frequency Inverters...

Reviews: