background image

S8VK-R

4

Engineering Data

Derating Curve

Mounting

Combinations with the S8VK-G

Power Boost Function

This function is possible when used in combination with S8VK-G (All 
Models).
Power Boost is a function that can output the temporary repeated 
boost current larger than the rated current. 
However, it should meet the following four Boost current conditions.
1. Time that the boost current flows: t1
2. The maximum value of the boost current: lp
3. The average output current: lave
4. The time ratio of the boost current flow: Duty

Note: Boost current conditions

Do not allow the boost current to continue for more than 10 
seconds.
Also, do not let the duty cycle exceed the boost current conditions.
These conditions may damage the Power supply.

Ensure that the average current of one cycle of the boost current 
does not exceed the rated output current.
This may damage the Power Supply.

Lessen the load of the boost load current by adjusting the ambient 
temperature and the mounting direction.

Power supply 

model

Redundant unit model

Redundancy

Higher capasity

S8VK-G015

@@

S8VK-R10

S8VK-R10

S8VK-G030

@@

S8VK-G060

@@

S8VK-G12024

S8VK-G24024

S8VK-R20

S8VK-G24048

S8VK-R20

S8VK-G48024

S8VK-G48048

Load r

atio (%)

Ambient temperature (°C)

A

B

C

40 

25

10  0  10 20 30 40 50 60 70  80

120 

100 

80 

60 

40 

20 

A: Standard mounting

B: Standard mounting, when contact mounted with S8VK-G

60°C and over: the derating is 2.5%/°C (when contact mounted 
with S8VK-G)

C: Face-up mounting

50°C and over: the derating is 1.25%/°C

(B) Contact Mounting

(C) Face-up mounting

(A) Standard (Vertical) mounting

S8VK-R

POWER SUPPLY
(S8VK-G)

[A] 

Ip: Boost current

Rated current

lave: Average current

t2 

t1 

output current

 t1 

 Ip 

 lave 

 10 s

 Rated boost current

 Rated current

Duty= 

t1 + t2

t1 

× 100 [%] 

≤ 

30%

Summary of Contents for S8VK-R Series

Page 1: ...0 1 Lloyd s standards 2 EMS EN61000 6 2 EMI EN61000 6 3 Six years warranty 3 1 The lifetime will depend on the connected power supply Refer to Functions on page 5 2 Scheduled to obtain certification i...

Page 2: ...r Lighting Voltage difference between Vin1 and Vin2 is less than 50 mV typ color green Others Ambient operating temperature 40 to 70 C Refer to Engineering Data Storage temperature 40 to 85 C Ambient...

Page 3: ...e load lines to these terminals 5 Status indicator redundancy OK Green Lighting Voltage difference between Vin1 and Vin2 is less than 2 4 V typ 6 Status indicator voltage balance Green Lighting Voltag...

Page 4: ...current of one cycle of the boost current does not exceed the rated output current This may damage the Power Supply Lessen the load of the boost load current by adjusting the ambient temperature and t...

Page 5: ...G03005 S8VK G06012 S8VK G12024 S8VK G240 S8VK G480 By adjusting the input voltage to light up LED the fluctuation of the output voltage will be less when one of the power supply breaks Chart 1 Operati...

Page 6: ...Stopper 3 5 3 6 dia Bit 1 4 7 Sliding 10 max 5 75 4 90 8 5 5 3 6 dia Bit 1 34 9 1 110 106 5 7 7 62 S8VK R10 10 5 0 dia Bit 2 5 0 dia Bit 2 1 4 112 2 117 8 34 7 6 35 4 7 Sliding 7 5 max 125 20 5 5 104...

Page 7: ...there is a possibility that the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35...

Page 8: ...Front mounting bracket for S8VK R10 S82Y VS10F Front mounting bracket for S8VK R20 S82Y VK10F Side mounting bracket for S8VK R10 S82Y VS10S Side mounting bracket for S8VK R20 S82Y VK10S 41 35 0 1 40 5...

Page 9: ...that exceeds the rated current of the signal output Installation Environment Do not use the Redundancy Unit in locations subject to shocks or vibrations In particular install the Redundancy Unit as f...

Page 10: ...te Note 1 The S8VK R may possibly be damaged from the impulse voltage if a testing device switch is used to abruptly apply or shut off 1 kV AC 0 5 kV AC Increase the applied voltage gradually using th...

Page 11: ...TE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of the prod...

Page 12: ...l 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Tokyo JAPAN O...

Reviews: