S
8
JX
9
S8JX-G
S8JX-P
Common Precautions
Input specification
100/200 V (Selected)
Item
Power ratings
*
1
300 W
600 W
Efficiency
5 V models
71% min.
72% min.
12 V models
75% min.
78% min.
24 V models
82% min.
80% min.
4
8
V models
82% min.
80% min.
Input
Voltage
*
2
100 to 120 VAC (allowable range: 85 to 132 VAC)
200 to 240 VAC (allowable range: 170 to 264 VAC)
(Switchable)
Frequency
*
2
50/60 Hz (47 to 450 Hz)
Current
*
3
100 V input
8 A max.
16 A max.(5V, 12V, 48V)
14 A max.(24V)
200 V input
4.5 A max.
9 A max.(5V, 12V, 48V)
8 A max.(24V)
Harmonic current emissions
---
Leakage current
*
3
100 V input
0.5 mA max.
200 V input
1 mA max.
Inrush current (for a
cold start at 25
°
C)
*
3
100 V input
25 A max.
30 A max.
200 V input
50 A max.
60 A max.
Output
*
4
Voltage adjustment range
*
5
−
10% to 15% (with V. ADJ) (48-V models:
±
10%)
Ripple
*
3
2.8% (p-p) max.(5V)
*
6
2% (p-p) max.(12V, 24V, 48V)
3.8% (p-p) max.(5V)
*
6
2% (p-p) max.(12V)
*
6
2% (p-p) max.(24V, 48V)
Input variation influence
0.4% max.
Load variation influence
0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence
0.05%/
°
C max.
Startup time
650 ms max.
500 ms max.
Hold time
*
3
20 ms min.
Additional
functions
Overload protection
*
7
105% to 175%
of rated load current, Inverted L voltage drop,
the circuit will be shut OFF when the
overload exceeds 5 s.(5V, 12V)
*
10
voltage drop, intermittent, automatic reset.
(24V, 48V)
105% to 175% of rated load current, Inverted
L voltage drop, the circuit will be shut OFF
when the overload exceeds 5 s.
*
10
Overvoltage protection
*
8
Yes (5V, 12V)
*
10
Yes (24V, 48V)
*
10
Yes
*
10
Overheat protection
Yes (5V, 12V)
*
10
N0 (24V, 48V)
*
10
Yes
*
10
Parallel operation
Yes (up to 5 units)
Series operation
Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator
Yes (color: red) (5V, 12V)
No (24V, 48V)
Yes (color: red)
Other
Ambient operating temperature
Refer to the derating curve in
Engineering Data
on page 17 (with no icing or condensation).
Storage temperature
−
25 to 65
°
C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA)
Insulation resistance
100 M
Ω
min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s
2
, 3 times each in
±
X,
±
Y,
±
Z directions
Output indicator
Yes (Color: Green)
EMI
Conducted Emissions
*
3
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
*
11
Radiated Emissions
Conforms to EN 55011 Group 1 Class A
*
11
*
12
EMS
Electrostatic Discharge
Conforms to EN61000-4-2
Radiated Electromagnetic Field
Conforms to EN61000-4-3
Electrical Fast Transient/Burst
Conforms to EN61000-4-4
Surge
Conforms to EN61000-4-5
Conducted Disturbance
Conforms to EN61000-4-6
Voltage Dips/Short Interruptions
Conforms to EN61000-4-11
Approved standards
*
13
UL UR: UL 508 (Recognition), UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
Weight
*
9
1,800 g max. (5V, 12V)
1,600 g max. (24V, 48V)
2,500 g max.
Summary of Contents for S8JX-G Series
Page 34: ...MEMO 34...