S8JC-Z
8
Engineering Data
Derating Curves for S8JC-Z
Derating Curves for S8JC-ZS
Note: 1.
Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading “A” in the above graph).
2.
If there is a derating problem, use forced air-cooling.
Terminal Arrangement
Terminal Cover Fitting
Load rate (%)
Ambient Temperature (
°
C)
-20 -10 0 10 20 30 40 50 60 70
120
100
80
60
40
20
0
A
Load rate (%)
Ambient Temperature (
°
C)
-20 -10 0 10 20 30 40 50 60 70
120
100
80
60
40
20
0
A
15-/35-/50-W Models
100-/150-/350-W Models
Note:
The S8JC-Z05024C is shown above.
Note: 1.
The S8JC-Z10024C is shown above.
2.
The rated current for output terminals is 25 A per terminal.
Be sure to use multiple terminals simultaneously for
current that exceeds the terminal rating. When applying a
current of 25 A or more, use at east two terminals each for
the positive and negative wires.
AC(L)
AC(N)
−
V
+
V
AC(L)
AC(N)
−
V
+
V
−
V
+
V
In (1) case, please push scratched parts (a, b) on the cover following the arrow “ ”
In (2) case, please remove the cover following the arrow “ ”
In (3) case, please remove the cover following the arrow “ ”
In (4) case, please push scratched parts (a, b) on the cover following the arrow “ ”
Removing
Fitting
a
b
a
b
(1)
(2)
(3)
(4)
S8JC-ZS
@@@@@
C Models
S8JC-ZS
@@@@@
C Models