S8JX
12
Construction and Nomenclature
Nomenclature
*1.
The fuse is located on the (L) side. It is NOT user-replaceable.
*2.
This is the protective earth terminal specified in the safety standards. Always ground this terminal.
Reference Values
15-/35-/50-/100-/150-W Models
E
D
A
C
B
+V
−
V
AC (L)
AC (N)
100 to 120 VAC
200 to 240 VAC
E
F
D
A
C
B
+V
−
V
AC (L)
Bottom
AC (N)
*1.
The fuse is located on the (L) side. It is NOT user-replaceable. For a DC
power input, connect the low side to the positive (+) terminal.
*2.
This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
No.
Name
Function
1
DC Output
Terminals (
−
V), (+V)
Connect the load lines to these terminals.
2
AC Input Terminals
(L), (N)
Connect the input lines to these terminals.
*
1
3
Protective Earth
Terminal (PE) (
)
Connect the ground line to these terminals.
*
2
4
Output Voltage
Adjuster (V. ADJ)
Use to adjust the voltage.
5
Output Indicator
(DC ON: Green)
Lights green while a direct current (DC) output is ON.
6
Input voltage switch
Switches the internal circuits according to the input
voltage.
"115V": 100 to 120 VAC
"230V": 200 to 240 VAC
Note:
The S8JX-G05024CD is
shown above.
Note:
The S8JX-G15005C is shown
above.
300-W Model
AC (L)
AC (N)
Bottom
+V
+V
−
V
−
V
E
F
D
C
H
A
B
600-W Model
AC (L)
AC (N)
Side
+V +V
−
V
−
V
G
E
F
D
A
C
H
B
No.
Name
Function
1
DC Output Terminals (
+
V), (
−
V)
Connect the load lines to these terminals.
2
AC Input Terminals (L), (N)
Connect the input lines to these terminals.
*
1
3
Protective Earth Terminal (PE) (
)
Connect the ground line to these terminals.
*
2
4
Input Voltage Selector Terminals
Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 230 VAC.
5
Output Indicator (DC ON: Green)
Lights while a Direct Current (DC) output is ON.
6
Output Voltage Adjuster (V. ADJ)
It is possible to increase or decrease the output voltage.
7
Protection-ON Alarm Indicator
(DC ON: Red)
The red indicator will be lit if the overvoltage (for a 600-W model) or overheat protection (for a 600-W model)
circuit is triggered. This indicator will also be lit when overload (for a 600-W model) is detected.
8
Selector of Parallel Operation
Set the selector to PARALLEL if the Units are in parallel operation.
Reliability (MTBF)
S8JX-G15012
@@
and S8JX-G15005
@@
Other models
240,000 hrs
250,000 hrs
Definition
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device
failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life expectancy
10 yrs. min.
Definition
The life expectancy indicates average operating hours under the ambient temperature of 40
°
C and a load rate of 50%.
Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.