Screwless Clamp Terminal Socket

 

PYF

@@S

Applicable Wires

Applicable Wire Sizes

0.2 to 1.5 mm

2

, AWG24 to AWG16

Applicable Wire Type

Solid wires, stranded wires, flexible wires, or wires with ferules can
be used.
(See note 1.) < 2.2 

 Diameter D (mm) 

 3.2 (3.5: see note 2.)

Conductor diameter d (mm) or length of sides a and b (mm) 

 1.9

Note: 1.

If the outer diameter D of the wire is less than 2.2 mm and
the exposed conductor length is less than 8 mm potentially
bad connection might occur in case wire is pushed to far in-
side. Please see following drawing.

2.

If the outer diameter D of the wire exceeds 3.2 mm, it might
be difficult to use double wiring.

Examples of Applicable Wires (Confirmed Using Catalog Information)

Wiring

Use wires of the applicable sizes specified above. The length of the
exposed conductor should be 8 to 9 mm.

Use the following wiring procedure.

1.

Insert the specified screwdriver into the release hole located
beside the wire connection hole where the wire is to be inserted.

2.

Insert the exposed conductor into the wire connection hole.

3.

Pull out the screwdriver.

Wires with Ferules

Type of wire

Conductor type

See note 1, above. Recommended wire sizes See note 2, above.

Equipment wire 2491X

Flexible

0.5, 0.75, 1.0 mm

2

1.5 mm

2

BS6004

Solid

0.5 mm

2

Switchgear BS6231

Solid

1.0 mm

2

1.5 mm

2

Switchgear BS6231

Flexible

0.5, 0.75 mm

2

1.0 mm

2

Tri-rated control and switchgear

Flexible

0.5, 0.75, 1.0, 1.5 mm

2

Conduit

Stranded

1.5 mm

2

UL1007

Flexible

18AWG

16AWG

UL1015

Flexible

18AWG, 16AWG

UL1061

Flexible

18AWG

UL1430

Flexible

18AWG

16AWG

Fig. 1 Exposed Conductor Length

8.5 ±0.5 mm

Wire connection holes

Fig. 2 Wire Connection Holes and Release Holes

Release holes

A

A

Wire connection hole

Fig. 3 Section A-A of Fig. 2

Release hole

Screwdriver

Insert

Insert

Pull out