52
Memobus Communication
Section 3-6
3-6-2
Memobus Parameter Settings
During configuration of the PROFIBUS Master unit the user must set a num-
ber of parameters, depending on the selected Communication block. De fig-
ure below shows the selection options for a Fixed Communication Block.
The parameter options are listed in the table below.
Parameter name
Range
(Hex)
Description
Fi
x
e
d Com
m
. Bl
oc
k
Device Address
00 ~ 1F
Defines the Memobus address of the device to exchange the I/O
data of this module with.
Read Status Register
0020
Address of the status register (Fixed).
Read Frequency Register
0023
Address of the Actual Frequency register (Fixed).
Read Voltage Register
0025
Address of the Actual Voltage register (Fixed).
Write Command Register
0001
Address of the Command register (Fixed).
Write Frequency Register
0002
Address of the Required Frequency register (Fixed).
Write Voltage Register
0003
Address of the Required Voltage register (Fixed).
F
le
x
ib
le
Co
mm.
Bl
o
c
k
Device Address
00 ~ 1F
Defines the Memobus address of the device to exchange the I/O
data of this module with.
Read Register Address One
0000 ~ FFFF
Address of first register to read from.
Read Register Address Two
0000 ~ FFFF
Address of second register to read from.
Read Register Address Three
0000 ~ FFFF
Address of third register to read from
Write Register Address One
0000 ~ FFFF
Address of first register to write to.
Write Register Address Two
0000 ~ FFFF
Address of second register to write to.
Write Register Address Three
0000 ~ FFFF
Address of third register to write to.