4. Operation
3-1. The UPS operation mode can be set if the power switch is turned ON while the beeper stop switch is
pressed.
Note: While in setting mode, output from the output receptacles are OFF, even if the power switch is ON.
How to make settings:
There are 3 items to select.
1) Cold start ON/OFF setting
2) Output voltage setting)
3) Signal input/output test
(1) When the beeper stop switch is briefly pressed (for less than 1 second), the next item is displayed.
(2) When the beeper stop switch is pressed and held (for more than 1 second), the unit enters the
“individual item setting mode”.
(3) When the power switch is turned OFF, setting mode quits and it returns to normal status (Status
No.2).
3. UPS operation mode settings
The settings available for this operation are shown below.
• Cold start ON/OFF setting
When ON, it is possible to start up the unit even when there is no AC input plug.
(It is not possible, however, to start up the unit by the remote signals.)
• Output voltage setting (100V/110V/115V/120V)
Four types of output voltage can be set for the output voltage during Battery Mode.
• Signal input/output test (BL/TR/BU/WB/BS/remote)
Test output can be made for four types of signals. The signal is output without causing an actual power
failure or internal malfunction. It is also possible to detect two types of signal input. The signal input from
the system can be checked on the LED display. (The unit does not actually stop, because it is in test
mode.)
Cold start ON/OFF setting
Output voltage setting
Signal input/output test