31
4. Operation
Status
indicator
No.
13
14
16
17
18
15
Battery
replacement
Beep
Output Charging
Description
Solution
Continuous
Continuous
Continuous
ON, or
OFF
—
—
OFF
OFF
OFF
Output stopped due to exceeded
connection capacity or a short-circuit with
the connected devices.
Stopped because of failure.
Stopped because of output voltage error
(over).
Continuous
—
OFF
Stopped because of output voltage error
(under).
Continuous
—
OFF
Stopped because of battery charge
voltage error (over).
Continuous
—
OFF
Stopped because of battery charge
voltage error (under).
4. Displays and beeps when there is an equipment failure
(continued)
indicates blinking
20
Intermittent
2-second
intervals
ON
ON
The battery test detected a weak battery.
Charge the battery.
You can replace the
weak battery with a
separately purchased
replacement battery
as needed.
Check that the AC
input of connected
devices is not short-
circuited, or that the
connection capacity
does not exceed the
rated capacity.
Details of error are
displayed only when
the “Beeper stop”
switch is pressed while
in status No. 14.
(Same as above.)
(Same as above.)
(Same as above.)
19
Continuous
—
OFF
Stopped because of abnormal internal
temperature.
(Same as above.)
Turn OFF this unit
and all connected
devices. Then, turn
the power switch
back ON for this unit
only. If the display
does not change,
there is a problem
with the UPS.
Contact the shop of
purchase or our
Electronic Systems &
Equipments customer
support center at: ____.
5. Display and beep for battery replacement
21
—
—
—
—
—
Cold start ON setting
UPS can start up even when there is no AC input
22
—
—
—
—
—
Cold start OFF setting
UPS can start up only when there is AC input
23
—
—
—
—
—
Output 100V mode
Output voltage is 100V (effective value)
24
—
—
—
—
—
Output 110V mode
Output voltage is 110V (effective value)
25
—
—
—
—
—
Output 115V mode
Output voltage is 115V (effective value)
26
—
—
—
—
—
Output 120V mode
Output voltage is 120V (effective value)
6. UPS operation mode setting display