83
References
A. Speci
fi
cations
Model
BN50S
BN75S
BN100S
BN150S
BN220S
BN300S
Method
Operation method
Cooling method
Connectable devices
Rated input voltage
Startup voltage range and
input voltage range
Input frequency
Maximum current
7A
10A
15A
20A
30A
42A
Phase
Input plug
Input protection
Input protection capacity
10A
13A
15A
25A
45A
45A
Output
Output voltage (In Battery Mode)
Output frequency (In Battery Mode)
Phase
Output waveform
Switching time
Backup time (*2)
5.5 min. or more 3.5 min. or more
5 min. or more
7 min. or more
5 min. or more
Type
Sealed lead battery life expectancy
Battery capacity (V/Ah/quantity)
Charging time
Environment
Dimensions *3
Weight of unit
Internal power consumption
Noise regulation (compliance standard)
Safety standard compliance
Noise
!4HRLZ\YL[OH[IV[O[OL=(]HS\LHUK[OL>]HS\LVM[OLSVHKJHWHJP[`JVUULJ[LK[V[OL<7:HYL^P[OPU[OLYHUNLZWLJPÄLKOLYL
*2: At ambient temperature of 20°C and with battery in initial state.
*3: The height includes the height of the rubber feet.
*6: When 20A plug is connected.
*7: When 50A plug or terminal block is connected.
*8: In 115V mode, the high voltage sensitivity setting is identical to the standard voltage sensitivity setting.
3kVA/2.7kW *7
*5: For BN300S, the maximum output (3.0kva/2.7kw) cannot be used with the standard input plug (NEMA L5-30P). To use with maximum output, replace with a 50A plug
(purchased separately) or perform terminal block connection (not compliant with UL standards).
The standard equipment input plug (NEMA L5-30P) cannot be connected to a household receptacle.
*4: For BN150S, the maximum output (1.5kva/1.35kw) cannot be used with the standard input plug (NEMA 5-15P). To use with maximum output, replace with a 20A plug
(purchased
separately).
45 dB max.
50 dB max.
Battery
Approx. 38 kg
12 V/ 8 Ah/ 2
12 V/ 8 Ah/ 4
12 V/ 8Ah/ 8
500VA/450W
750VA/680W
1kVA/0.9W
1.5kVA/1.35kW
*6
Natural air cooling
Line-interactive method
Forced air cooling
PC, display, and peripherals
Output receptacle
Single-phase, two-wire
50/60Hz±0.1Hz
Single-phase, two-wire
Sine wave
18% or less
NEMA 5-15R
x 6 receptacles
NEMA 5-15P *4
Input
100V mode 100 VAC±6%
115V mode 110 VAC ±6%
100V mode
89±2 to 118±2 VAC
84±2 to 118±2 VAC
89±2 to 113±2 VAC
99±2 to 129±2 VAC
94±2 to 129±2 VAC
*8
115V mode
50/60Hz±4Hz
Reset-type overcurrent protection device
2.2kVA/1.98kW
100 to 115 VAC
NEMA L5-30P *5
Output capacity (shared maximum) *1
NEMA 5-20R x 2 receptacles
NEMA 5-15R x 8 receptacles
10 msec. max.
4 to 5 years (long operating life) *At ambient temperature of 20°C
Compact sealed lead battery
8 hours
0 to 40°C/ 25 to 85%RH
-15°C to 50°C/ 10 to 90%RH *With battery fully charged, and with no condensation
148 x 362 x 203 (±1)mm
175 x 415 x 238 (±1)mm
200 x 411 x 405 (±1)mm
UL1778
Approx. 10 kg
Approx. 22 kg
Normal: 30W, Max.: 70W
Normal: 60W, Max.: 150W
Normal: 100W, Max.: 250W
VCCI Class B
VCCI Class A
Standard sensitivity setting Low voltage sensitivity setting
High voltage sensitivity setting
Standard sensitivity setting Low voltage sensitivity setting
High voltage sensitivity setting
100V mode
90±2 to 112±2 VAC
85±2 to 112±2 VAC
92±2 to 108±2 VAC
100 to 125±2 VAC
95 to 125±2 VAC
*8
115V mode
Standard sensitivity setting Low voltage sensitivity setting High voltage sensitivity setting
Standard sensitivity setting Low voltage sensitivity setting
High voltage sensitivity setting
Output voltage
(In Commercial Power Mode)
Output frequency
(In Commercial Power Mode)
Input frequency through output
Waveform distortion rate
9LJ[PÄLKSVHKH[YH[LKV\[W\[
Operating environment temperature/
humidity
Storage environment temperature/
humidity
7.9 min. or more