2-3
Setting of FINS Node Address of
Built-in EtherNet/IP Port
This FINS node address is necessary to identify a node in the FINS communication.
The following describes how to determine the FINS node address of the built-in EtherNet/IP port and
how to set the FINS node address from the Sysmac Studio.
IP address
⇔
FINS
node address conver-
sion method
FINS node address determina-
tion method
Setting method from Sysmac Studio
Automatic generation
method
The least significant digits of the
IP address becomes the FINS
node address automatically.
Controller Setup
-
Built-in EtherNet/IP Port
Settings
-
TCP/IP Settings
-
IP Address
Settings
Combined method
Set the FINS node address itself.
Controller Setup
-
Built-in EtherNet/IP Port
Settings
-
FINS Settings
-
FINS Node
Address Settings
IP address table method
*1.
This may vary depending on the setting of
IP address
⇔
FINS address conversion method
for FINS/
UDP. To make the setting, select
Configurations and Setup
-
Controller Setup
-
Built-in EtherNet/IP Port
Settings
-
FINS Settings
-
FINS/UDP
-
IP Address
⇔
FINS Address Conversion Method
from the Multi-
view Explorer of the Sysmac Studio.
When the automatic generation method is selected, the least significant digit of the IP address is set
as the FINS node address.
When the combined method or IP address table method is selected, the value specified for the FINS
node address setting is the FINS node address.
2 Server Function
2 - 5
NX-series CPU Unit FINS Function User's Manual (W596)
2-3 Setting of FINS Node Address of Built-in
EtherNet/IP Port
2
Summary of Contents for NX102-10 Series
Page 24: ...Sections in this Manual 22 NX series CPU Unit FINS Function User s Manual W596...
Page 36: ...2 Server Function 2 6 NX series CPU Unit FINS Function User s Manual W596...
Page 40: ...2 Server Function 2 10 NX series CPU Unit FINS Function User s Manual W596...
Page 65: ...I Index I 1 NX series CPU Unit FINS Function User s Manual W596 I...
Page 67: ......