Event name
Cast Error
Event code
55010000 hex
Meaning
A casting error was detected.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
In DEBUG
mode (RUN) or
RUN mode
Error attrib-
utes
Level
Minor fault
Recovery
Automatic re-
covery
Log category
System
Effects
User program
Continues.
Operation
The CPU Unit executes NX bus communications
but execution of the user program stops. (All I/O
data will remain at 0.)
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
A value was input that exceeded
the range of the receiving varia-
ble.
Do not allow the value to exceed
the range of the receiving varia-
ble.
Perform the following corrections
according to the operating mode
of the Safety CPU Unit.
•
RUN mode: Change to PRO-
GRAM mode and transfer the
corrected user program.
•
DEBUG mode (RUN): Change
to PROGRAM mode and
transfer the corrected user
program.
Program operation considering
the corrections that are given on
the left.
Attached in-
formation
Attached infor-
mation 1:
Error details
0x01000ADF: The conversion between the signed and unsigned data types was failed.
0x01000AE0: The positive upper limit of the data type after conversion was exceeded.
0x01000AE1: The negative upper limit of the data type after conversion was exceed-
ed.
Precautions/
Remarks
The CPU Unit executes NX bus communications but execution of the user program stops. (All I/O data
will remain at 0.)
12 Troubleshooting
12 - 54
NX-series Safety Control Unit User's Manual (Z930)
Summary of Contents for NX-SIH400
Page 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Page 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Page 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Page 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Page 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Page 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Page 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Page 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Page 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Page 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Page 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Page 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Page 625: ......