5-6 Initialization/Setting Screen
5-32
Initial Label
This function is used to set and display the label number that is shown on the screen when
the NS-Runtime is started.
The initial number can be set to between 0 to (the number of label minus 1).
Set and display the label number by using operations from the Project Tab Page as follows.
1. The label number that is shown on the screen when the NS-Runtime is started will be
displayed on the Initial Label field.
2. To change the initial label, input the label number. The value can also be input using a
keypad that is displayed by clicking the keyboard button.
3. After setting, click the
Write
Button to save the setting. (For details on the write button,
refer to
Writing
on page 5-29.)
N
N
N
o
o
o
t
t
t
e
e
e
This initial label number can also be set from the CX-Designer.
Alarm/Event History Recording Method
This function is used to display the method for recording the alarm/event histories.
The alarm/event history recording method is read-only and cannot be edited.
This alarm/event history recording method is set from the CX-Designer.
If a ring buffer is used, when the specified number of records is exceeded, the oldest data is
deleted and the new data is recorded.
If the ring buffer is not used, the NS-Runtime stops collecting history data when the specified
number of records has been reached. Initialize the alarm/event histories to reopen the
history records.
N
N
N
o
o
o
t
t
t
e
e
e
For details on initializing the alarm/event histories, refer to
Initializing and Saving the
Alarm/Event History
in this manual.
Data Log Recording Method
This function is used to display the data log recording method.
The data log recording method is read only and cannot be edited.
The use of a ring buffer for the data log recording method is fixed.
When the specified number of log entries is exceeded, the oldest data is deleted and the
new data is recorded.
Use the CX-Designer to set the number of log entries.
N
N
N
o
o
o
t
t
t
e
e
e
For information on the data log, refer to
Initializing and saving the Data Log
in this manual
and
2-20-3 Data Log Function
in the NS Series Programming Manual.
Summary of Contents for NS-NSRCL Series
Page 1: ...Cat No V093 E1 05 NS Runtime Software USER S MANUAL...
Page 2: ......
Page 28: ...1 4 Comparison between the NS Series and the NS Runtime 1 14...
Page 38: ...2 6 User Interface 2 10...
Page 56: ...3 5 Converting Projects 3 18...
Page 84: ...4 5 Macros 4 28...
Page 136: ...5 11 Window Size 5 52...
Page 154: ...7 3 Error Messages and Countermeasures 7 6...
Page 156: ......
Page 157: ......