background image

General-purpose Relays

 

MK-S New Model

3

Specifications

Ratings

Coil Ratings

Note: 1.

The rated current and coil resistance are measured at a coil temperature of 23

°

C with tolerances of +15%/

20% for AC rated current and

±

15% for DC coil resistance.

2.

Performance characteristic data are measured at a coil temperature of 23

°

C.

3.

The maximum voltage is one that is applicable instantaneously to the Relay coil at 23

°

C and not continuously.

4.

For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.

Contact Ratings

Rated voltage

Rated current

Coil resistance

Must operate 

voltage

Must release 

voltage

Max. voltage

Power 

consumption

50 Hz

60 Hz

AC

6 V

443 mA

385 mA

3.1 

80% max. of rated 
voltage

30% min. of rated 
voltage at 60 Hz
25% min. of rated 
voltage at 50 Hz

110% of rated volt-
age

Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz

12 V

221 mA

193 mA

13.7 

24 V

110 mA

96.3 mA

48.4 

100 V

26.6 mA

23.1 mA

760 

110 V

24.2 mA

21.0 mA

932 

200 V

13.3 mA

11.6 mA

3,160 

220 V

12.1 mA

10.5 mA

3,550 

230 V

10.0 mA

11.5 mA

4,250 

240 V

11.0 mA

9.6 mA

4,480 

DC

6 V

224 mA

26.7 

15% min. of rated 
voltage

Approx. 1.4 W

12 V

112 mA

107 

24 V

55.8 mA

430 

48 V

28.1 mA

1,710 

100 V

13.5 mA

7,390 

110 V

12.3 mA

8,960 

Load

Resistive load
(cos

φ 

= 1)

Inductive load
(cos

φ 

= 0.4)

Contact mechanism

Single

Contact material

AgSnIn

Rated load

NO

10 A, 250 VAC
10A, 30 VDC

7 A, 250 VAC

NC

5 A, 250 VAC
5 A, 30 VDC

Rated carry current

10 A

Max. switching voltage

250 VAC, 250 VDC

Max. switching current

10 A

Max. switching power

NO

2,500 VA/300 W

NC

1,250 VA/150 W

Summary of Contents for MK-S - 2

Page 1: ...Blank Mechanical indicator I Mechanical indicator and lockable test button 4 LED Indicator Blank Standard N LED indicator 5 Coil Polarity Blank Standard 1 Reverse polarity DC coil only 6 Surge Absorp...

Page 2: ...standard MKS2PN D 2 MKS2PIN D 2 3PDT Standard MKS3PN D MKS3PIN D Non Standard MKS3PN D 2 MKS3PIN D 2 MKS3PN D 5 MKS3PIN D 5 Models with Varistor DPDT Standard MKS2P V MKS2PI V AC Non standard MKS2P V...

Page 3: ...0 Hz 60 Hz AC 6 V 443 mA 385 mA 3 1 80 max of rated voltage 30 min of rated voltage at 60 Hz 25 min of rated voltage at 50 Hz 110 of rated volt age Approx 2 3 VA at 60 Hz Approx 2 7 VA at 50 Hz 12 V 2...

Page 4: ...ngle amplitude 1 5 mm double amplitude Malfunction 10 to 55 to 10 Hz 0 5 mm single amplitude 1 0 mm double amplitude Shock resistance Destruction 1 000 m s2 approx 100 G Malfunction 100 m s2 approx 10...

Page 5: ...urning Round terminals cannot be used for finger protection models Use Y shaped terminals 52 5 max 34 5 max 34 5 max 0 8 34 5 max 34 5 max 52 5 max 0 8 Socket Surface mounting Socket for track or scre...

Page 6: ...0 A2 9 34 3 14 4 12 8 32 38 8 30 Terminal Arrangement Mounting Holes Two M4 or two 4 5 dia hole Eight M4 screws PFC A1 4 6 62 60 8 4 5 6 2 pieces per set 4 5 15 25 25 25 25 10 10 1000 500 7 3 0 15 35...

Page 7: ...2 MKS3P I 1 D 5 Models with LED indicator DC Coil MKS2P I N D MKS2P I N D 2 MKS3P I N D MKS3P I N D 2 MKS3P I N D 5 Bottom View 1 2 3 4 5 6 7 8 8 6 3 1 2 7 4 5 1 2 3 4 5 6 7 8 10 11 9 9 11 10 8 7 6 5...

Page 8: ...tary testing position and go straight into the locked position Use an insulated tool when you operate the test button Models with test buttons or LED indicators fulfill the requirements for reinforced...

Page 9: ...General purpose Relays MK S New Model 9...

Page 10: ...10 General purpose Relays MK S New Model...

Page 11: ...General purpose Relays MK S New Model 11...

Page 12: ...he product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROP...

Reviews: