46
3.
Basic use
3.4 How to read the setting values (continued)
■
Setting item list
MENU No.
Setting Item
Main display
Display of options and input values
Default
Value
Remarks
Circuit
A
A1
Phase and wire type
3P4W / 1P2W /1P3W / 3P3W /1P2W2 /
1P3W2
3P4W
3P4W: 3-phase 4-wire, 1P2W: 1-phase 2-wire
1P3W: 1-phase 3-wire, 3P3W: 3-phase 3-wire
1P2W2: 1-phase 2-wire voltage selected
1P3W2: 1-phase 3-wire composite
A2
Communication address
Modbus : --, 01 to 99
CompoWay/F : -- 00 to 99
01
Set a different number for each circuit.
A3
Current on the CT
secondary side
1A / 5A
5A
Set to match the rating of the CT to be used.
A4
Current on the CT primary
side
1 to 99999
5
Rated values for the primary side of the CT to be
connected.
Set CT individually.
A5
Voltage assignment
V_R / V_T / V_R-T
V_R
Set the voltage phase for 1-phase 2-wire circuits
when 1P2W2 is selected.
A6
Pulse output ON/OFF
ON / OFF
OFF
A7
Active energy reset
-----
-----
Clear the active energy for the circuit.
Circuit
B
B0
Circuit B ON/OFF
ON / OFF
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not possible.
B1
Phase and wire type
The phase and wire type set by menu No.
A1 is displayed.
Phase and wire type set in MENU No. A1
B2
Communication address
Modbus : --, 01 to 99
CompoWay/F : -- 00 to 99
Automatic
S/N
Set a different number for each circuit.
B3
Current on the CT
secondary side
1A / 5A
5A
Set to match the rating of the CT to be used.
B4
Current on the CT primary
side
1 to 9999
5
Rated values for the primary side of the CT to be
connected.
Set CT individually.
B5
Voltage assignment
V_R / V_T / V_R-T
V_R
Set the voltage phase for 1-phase 2-wire circuits
when 1P2W2 is selected.
B6
Pulse output ON/OFF
ON / OFF
OFF
B7
Active energy reset
-----
-----
Clear the active energy for the circuit.
Circuit
C
C0
Circuit B ON/OFF
ON / OFF
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not possible.
C1
Phase and wire type
The phase and wire type set by menu No.
A1 is displayed.
Phase and wire type set in MENU No. A1
C2
Communication address
Modbus : --, 01 to 99
CompoWay/F : -- 00 to 99
Automatic
S/N
Set a different number for each circuit.
C3
Current on the CT
secondary side
1A / 5A
5A
Set to match the rating of the CT to be used.
C4
Current on the CT primary
side
1 to 9999
5
Set CT individually.
C5
Voltage assignment
V_R / V_T / V_R-T
V_R
Set the voltage phase for 1-phase 2-wire circuits
when 1P2W2 or 1P3W2 is selected.
C6
Pulse output ON/OFF
ON / OFF
OFF
C7
Active energy reset
-----
-----
Clear the active energy for the circuit.
Circuit
D
D0
Circuit B ON/OFF
ON / OFF
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not possible.
D1
Phase and wire type
The phase and wire type set by menu No.
A1 is displayed.
Phase and wire type set in MENU No. A1
D2
Communication address
Modbus : --, 01 to 99
CompoWay/F : -- 00 to 99
Automatic
S/N
Set a different number for each circuit.
D3
Current on the CT
secondary side
1A / 5A
5A
Set to match the rating of the CT to be used.
D4
Current on the CT primary
side
1 to 9999
5
Set CT individually.
D5
Voltage assignment
V_R / V_T / V_R-T
V_R
Set the voltage phase for 1-phase 2-wire circuits
when 1P2W2 or 1P3W2 is selected.
D6
Pulse output ON/OFF
ON / OFF
OFF
D7
Active energy reset
-----
-----
Clear the active energy for the circuit.