K8DT-LS

5

Nomenclature

Front Panel

Note:

Use solid wires, stranded wires, or ferrules to connect to the 
terminals.
To maintain the withstand voltage after connecting the 
terminals, insert 8 mm of exposed conductor into the terminal.

Indicators

Setting Knobs

Operation Method

Connections

Outputs

For a relay output, the 

SPDT

 contacts are output on terminals 11, 12, and 14. For a transistor output, the output is on terminals 11 and 14.

The internal circuit of the transistor output is NPN, but application is possible for either a sinking or sourcing output.

DIP Switch Settings

The operating mode is set using the DIP switch located on the front of the Unit.
K8DT-LS does not use SW2, SW3 and SW4.

Note:

Open the DIP switch cover to set the DIP switch.
Keep the DIP switch cover closed while the power supply to the Relay is ON.

Operating time kno

b

Operating resistance kno

b

Po

w

er indicator

O

u

tp

u

t stat

u

s indicator

Terminal 

b

lock

(See note.)

Terminal 

b

lock

(See note.)

8

 mm

8

 mm

Solid 

W

ire

8

 mm

Stranded 

W

ires

Ferr

u

les

Item

Description

Power indicator (PWR: 
Green)

Lit when power is being supplied.

Output status indicator 
(Output: Yellow)

Lights for output.

Item

Description

Operating resistance knob

Used to set the resistance to 10 k to 
100 k

Ω

.

Operating time knob

Used to set the operating time to 0.1 to 
10 s.

load

K

8

DT

11

Sinking

In the case of sinkin

g

 output applications

14

load

K

8

DT

11

In the case of sourcin

g

 output applications

14

So

u

rcing

O

N

1

2

3

4

SW3

DIP switch pins

SW2
SW1

SW4

DIP Switch Function

Note:

All pins are set to OFF by default.

Pin

ON  

 

OFF  

 

Operating mode

Automatic liquid 
discharge 
operation

Not used.

Not used.

Not used.

Automatic liquid 
supply operation

1

O

N

OFF

2

3

4

Summary of Contents for K8DT-LS Series

Page 1: ...h bare stranded wires Double insertion holes for crossover wiring all terminals UL listed for easy shipping to North America Models with transistor outputs added for low contact wear Ordering Informat...

Page 2: ...esistance against corrosion For installation at long distances from the liquid level Model PS 3S 4S 5S PS 31 SUS304 300 mm BF 1 BF 3 5 BS 1 BS 1T PH 1 2 Appearance Application Purified water service i...

Page 3: ...insertion force 15 N Wire stripping length 8 mm Ferrule length 8 mm Recommended flat blade screwdriver XW4Z 00B Omron SZF 0 4 2 5 Phoenix Contact 210 719 Wago SDI 0 4 2 5 75 Weidmuller Current capacit...

Page 4: ...E3 E2 DIP SW Power supply AC DC Power supply AC DC Water or other liquid Water or other liquid Three phase power supply Motor Pump Motor Pump Source of liquid Source of liquid Pump motor protection m...

Page 5: ...witch Keep the DIP switch cover closed while the power supply to the Relay is ON Operating time knob Operating resistance knob Power indicator Output status indicator Terminal block See note Terminal...

Page 6: ...g 17 5 90 86 90 5 100 Conductive Level Controller K8DT LS Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parentheses are for the PFP 50N...

Page 7: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Page 8: ...emember that the power supply terminals carry a high voltage 21 The product must be handled only by trained electrician 22 Prior to operation check the wiring before you supply power to the product 23...

Page 9: ...emove the flat blade screwdriver from the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the...

Page 10: ...ulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the input terminals a...

Page 11: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 12: ...9 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyo...

Reviews: